GoodmanHPCtrl

ESP32-based controller for Goodman heatpumps with support for cooling, heating, and defrost modes.

Web Interface

Page Screenshot
Home Home
Dashboard Dashboard
Pins Pins
Configuration Configuration
OTA Update OTA Update
Log Log
Heap Heap

Features

  • Relay control — 4 output pins (FAN, Contactor, W-Heat, Reversing Valve) driven by 4 input signals (Low Pressure Switch, Defrost, Y-Cool, O-Heat)
  • Temperature monitoring — Up to 6 OneWire (Dallas DS18B20) sensors (compressor, suction, ambient, condenser, liquid, vapor) + liquid line thermocouple fallback with auto-detection priority: MAX6675 SPI > MAX31850K OneWire > MCP9600 I2C. OneWire sensors discovered on the bus are automatically merged with saved config on boot — new devices get default names and appear immediately without a config reset
  • Subcooling calculation — Real-time subcooling diagnostic (CONDENSER_TEMP - LIQUID_TEMP) displayed on dashboard when both sensors are valid and compressor is running. Relevant for TXV systems to verify proper refrigerant charge
  • Ambient temp fallback — 3-tier failover chain for ambient temperature: local OneWire sensor → weather data (MQTT subscription or OpenWeatherMap HTTP API, or both simultaneously) → ESP32 internal die temp. Actively fails up to the best available source every cycle. Configurable staleness timeout, test failover button, dashboard source indicator
  • Remote access — REST API, WebSocket, MQTT (QoS 1), and CAN bus for monitoring and control
  • HTTPS/SSL — Self-signed ECC P-256 certificate on port 443 for secure /config, /update, and /ftp endpoints. Graceful fallback to HTTP-only if no certs found on SD card
  • Dark/light theme — Configurable dark/light theme with shared theme.css stylesheet. Persisted to SD card config, cached in localStorage for flash-free page loads. Instant preview on config page
  • Admin password protection — HTTP Basic Auth on sensitive endpoints (/config, /update, /ftp). No password = open access
  • Password encryption — All passwords (WiFi, MQTT, admin, FTP) encrypted at rest on SD card
  • Live dashboard — Real-time dashboard at /dashboard with state banner, protection status pills with dynamic labels (LPS No Fault/Fault, Temp Ok/Low Temp, Comp Ok/OT, Suct LT Ok/LT, Suct Temp/High Suct with live temp reading, RV Pass/Fail with inline clear button), input/output grid, temperatures, and reboot button. Output indicators include inline status pills:
    • SC SC (Short Cycle) — Shown on CNT output. Green when inactive, red when CNT short cycle protection delay is active (CNT was off < 5 min, waiting 30s before reactivation)
    • DFH DFH (Defrost Hold) — Shown on CNT, W, and RV outputs during the 3-phase defrost entry and exit transitions. On RV and W: red during entry Phase 1 or exit Phase 1 (pressure equalization). On CNT: red during entry Phase 2 or exit Phase 2 (waiting for CNT short cycle before compressor starts)
  • Pin table with manual override — Auth-protected /pins page showing all GPIO inputs, outputs, and temperatures in a table. "Normal Mode Lockout" checkbox enables manual output control, bypassing the state machine for up to 30 minutes (auto-timeout). CNT enforces short cycle protection even in manual mode. Single auth prompt covers the entire lockout session. "Force Defrost" button triggers a software defrost cycle from HEAT mode (requires no active faults or manual override)
  • Temperature history — Configurable CSV logging interval (30s-5min, default 2min) per sensor to SD card (/temps/<sensor>/YYYY-MM-DD.csv), rolling Canvas line charts on dashboard (6 sensors) with 1h/6h/24h/7d timeframe selector, auto-purge after 31 days
  • Web-based configuration — HTML pages served from /www/ on SD card for configuration, OTA updates, and monitoring
  • FTP server — SimpleFTPServer with timed enable/disable (10/30/60 min) from config page. Configurable password (encrypted on SD card); defaults to admin/admin when not set. Defaults to OFF; auto-disables after timeout
  • OTA updates — Firmware upload saves to SD card (/firmware.new), then apply to flash. Automatically backs up running firmware with build date metadata before flashing. Supports manual revert and automatic crash recovery (see Crash Recovery)
  • SD card configuration — WiFi, MQTT, and sensor settings stored as JSON on SD card
  • Multi-output logging — Serial, MQTT, SD card with tar.gz compressed log rotation, and WebSocket streaming
  • In-memory log buffer — 500-entry ring buffer in PSRAM, accessible via /log API endpoint
  • NTP time sync — Automatic time synchronization from NTP servers, refreshes every 2 hours
  • I2C bus — Initialized on GPIO8 (SDA) / GPIO9 (SCL) with automatic device scan at startup and /i2c/scan API endpoint
  • PSRAM support — All heap allocations routed through PSRAM when available
  • WiFi AP fallback — Configurable timeout (default 10 minutes) before switching to Access Point mode for OTA recovery and reconfiguration
  • CAN bus integration — Optional CAN bus (ESP32 TWAI, 250 kbps) replaces physical Y/O thermostat wires with CAN messages from AThermostat. Publishes HP state, temperatures, and heartbeat. 10-second timeout safety shuts down compressor if CAN communication is lost. DFT/LPS safety inputs always remain physical. Configurable via can.enabled in config JSON. See docs/canbus-goodmanhp-implementation.md
  • Multi-unit support — Configurable system name (max 20 chars, alphanumeric + spaces) and MQTT topic prefix. System name is used as the web UI brand, AP SSID, OLED display name, HTTPS auth realm, and SSL certificate CN. Multiple controllers can publish to the same MQTT broker with unique prefixes (e.g., unit1/temps, unit2/temps)
  • FreeRTOS compatible — Uses vTaskDelay() instead of delay() for proper RTOS task yielding

Architecture

GoodmanHP Controller

The GoodmanHP class is the central controller that manages all I/O pins and the heat pump state machine:

  • Pin Management — Maintains std::map collections for input and output pins

    • addInput(name, pin) / addOutput(name, pin) — Register pins
    • getInput(name) / getOutput(name) — Access individual pins
    • getInputMap() / getOutputMap() — Access full pin collections
  • Startup — All outputs (FAN, CNT, W, RV) are turned OFF on controller startup

  • State Machine — Tracks heat pump operating mode:

    • OFF — No active request
    • HEAT — Y input active (heating mode, RV off, W off)
    • COOL — Y and O inputs active (cooling mode, RV on, W off)
    • DEFROST — DFT emergency defrost or software defrost cycle (W on)
    • ERROR — Fault condition active (LPS low pressure); CNT shut down, W follows Y in HEAT mode (Y active, O not active), state updates blocked until fault clears
    • LOW_TEMP — Ambient temperature below threshold (default 20°F) for 10 continuous minutes; compressor off, auxiliary heat (W) on, auto-recovers when temp stays above threshold for 10 minutes
  • Output Control by State:

    • RV (reversing valve): ON in COOL, OFF in HEAT/OFF
    • W (auxiliary heat): ON in DEFROST, ERROR (HEAT mode only), LOW_TEMP (HEAT mode only), and RV_FAIL (HEAT mode only); OFF otherwise. In COOL mode (Y+O), the system will not operate below 20°F
    • CNT (contactor): auto-activates when Y input becomes active, with short cycle protection: if CNT was off for less than 5 minutes, a 30-second delay is enforced before reactivation; if off for 5+ minutes, CNT activates immediately
  • Compressor Over-Temperature Protection — When COMPRESSOR_TEMP reaches 240°F or above:

    • Immediately shuts down CNT to stop compressor
    • Keeps FAN running to cool the compressor
    • Blocks CNT activation while overtemp is active
    • Rechecks compressor temp every 1 minute
    • Auto-recovers when temp drops below 190°F (50°F hysteresis gap)
    • Logs fault condition and resolution time
    • Highest priority fault — checked before LPS and ambient temp
  • FAN Airflow Safety (Current Watchdog) — Guarantees the outdoor fan is actually moving air whenever the compressor (CNT) is energized. See BUG-013 for the field failure that motivated this protection:

    • CNT ⇒ FAN invariant — every code path that turns CNT ON also asserts FAN ON in the same block (state transitions, HEAT↔COOL cancel path, short-cycle re-activation, updateState() output validation) so the outputs cannot desynchronize
    • Current-based livenessFAN_CURRENT (SCT-013-030 CT on ADS1115) is polled while CNT is on; if it stays below FAN_MIN_RUNNING_AMPS (default 0.3 A) for FAN_NO_CURRENT_TIMEOUT_MS (default 20 s), CNT is shut down and the controller latches ERROR state for FAN_FAULT_ERROR_MS (default 3 min)
    • Debounced — requires 3 consecutive low reads before arming the 20 s timer, filtering single-sample I2C glitches from bus contention with WiFi / AsyncTCP / SD log flush
    • Auto-recovers after the 3-minute lockout; the watchdog re-arms on the next CNT activation and re-latches if the fan still draws no current
    • Blocks CNT re-activation while the lockout is active; public accessors: isFanFaultActive(), getFanFaultRemainingMs(), clearFanFault()
    • Emits grep-friendly FAN_FAULT: and FAN_SAFETY: log tags with Y=, O=, state=, amps=, pin=, elapsed= for post-mortem log forensics
    • Depends on CurrentSensor producing trustworthy RMS: 60-sample window over ~4 line cycles, DC-mean subtraction, and all-zero I2C reads rejected as invalid rather than published as 0.00 A
  • Suction Low-Temperature Protection (COOL mode only) — Monitors SUCTION_TEMP for freezing conditions:

    • Warns when suction temp drops below 34°F
    • Shuts down CNT below 32°F (critically low), keeps FAN running
    • Blocks CNT activation while fault is active
    • Rechecks every 1 minute
    • Auto-recovers when temp rises above 40°F (8°F hysteresis from critical)
    • Auto-clears if mode changes away from COOL
    • Logs fault condition and resolution time
  • LPS Fault Protection — When the LPS (Low Pressure Switch) input goes LOW:

    • Immediately shuts down CNT if running
    • Sets state to ERROR, blocking all state updates
    • Blocks CNT activation while fault is active
    • W (auxiliary heat) continuously follows Y during active fault: ON when Y active and O not active (HEAT mode), OFF when Y drops or O active (COOL mode). W is never turned on in COOL mode
    • Auto-recovers when LPS goes HIGH; W turned off, short-cycle protection (30s delay) is enforced on CNT reactivation
    • Publishes fault events via MQTT (goodman/fault topic)
  • Low Ambient Temperature Protection — When AMBIENT_TEMP drops below the configurable threshold (default 20°F):

    • 10-minute validation delay in both directions: temp must stay below threshold for 10 continuous minutes before entering LOW_TEMP, and above threshold for 10 continuous minutes before exiting. If temp reverses during the validation window, the pending transition is cancelled. Prevents fluttering near the threshold
    • Enters LOW_TEMP state: shuts down CNT, turns off FAN and RV
    • Turns on W (auxiliary heat) in HEAT mode only
    • If thermostat switches to COOL mode (Y+O) while in LOW_TEMP, W is turned off — no heating or cooling operates below 20°F in COOL mode
    • Blocks all compressor activation (CNT) while ambient temp is too low
    • Auto-recovers when temperature stays above threshold for 10 minutes
    • Threshold is configurable via lowTemp.threshold in SD card config
  • Ambient Temperature Fallback (3-Tier) — When the local AMBIENT_TEMP OneWire sensor is unavailable, the system falls through a priority chain to maintain ambient awareness:

    1. Local sensor (primary) — OneWire DS18B20, highest accuracy
    2. Weather data (failover) — Cached outdoor temperature from a configurable source:
      • MQTT: Subscribes (QoS 1) to a configurable topic (e.g., homeassistant/sensor/outdoor_temp/state) and parses plain float payloads
      • HTTP: Polls OpenWeatherMap API at a configurable interval (default 10 min, range 1–60)
      • MQTT + HTTP: Both run simultaneously — MQTT delivers faster push updates while HTTP acts as a safety net if MQTT stops publishing. Most recent update from either source wins
    3. ESP32 internal temp (last resort) — Die temperature via temperatureRead(), converted C→F. Reads higher than true ambient but catches genuinely cold conditions
    • Fail-up: The fallback chain re-evaluates every 10s cycle and actively promotes to the best available source — INTERNAL→WEATHER when weather data arrives, any fallback→SENSOR when the real sensor recovers
    • Weather data is cached with a configurable staleness timeout (default 30 minutes). Stale weather with no local sensor falls through to ESP32 internal temp
    • ambientSource field in /state JSON and MQTT state tracks the active source: "sensor", "weather", or "internal"
    • Dashboard shows a source-aware ambient pill (green for sensor, orange for weather/internal) and a "Weather Amb (failover)" row with the cached temperature and age
    • Output state validator enforces CNT OFF when no ambient data is available (sensor invalid + no weather)
    • Config page "Weather Ambient Fallback" fieldset: source dropdown (None/MQTT/HTTP/MQTT + HTTP), conditional MQTT topic or HTTP API key/ZIP/country fields, staleness timeout
    • Test Failover button on config page forces the ambient sensor offline for 30 minutes to verify the fallback chain
    • Configured via weather section in SD card config JSON. API key encrypted with same $AES$/$ENC$ scheme as other passwords
  • Input Pin Validation Delay — All 4 input pins (LPS, DFT, Y, O) use a configurable debounce/validation delay (default 2 seconds) to prevent false triggers from electrical noise or transient signals:

    • Input pins are polled every 500ms via onCheckInputQueue() (direct GPIO polling, no ISR attachment required)
    • When a pin's live GPIO state differs from its confirmed state, a validation timer starts
    • After the delay expires, the GPIO is re-read to confirm the pin is still in the expected state
    • If the pin has reverted to its original state, the change is discarded as a false trigger and logged as a warning
    • isActive() returns the confirmed/debounced state, not the live GPIO — the state machine only sees validated inputs
    • getPendingState() prevents re-triggering while a validation is already in progress
    • Both activation (pin going HIGH) and deactivation (pin going LOW) go through the full delay
    • Configurable via heatpump.inputDelay.ms in config JSON (0–60 seconds, live — changes apply immediately to all input pins)
  • State Validation Delay — After any state transition (e.g., OFF→HEAT, HEAT→COOL), the system holds the new state for a configurable period (default 30 seconds) before allowing another normal-priority state change. This prevents rapid state cycling:

    • HIGH priority states (OFF, ERROR) bypass the validation timer entirely
    • NORMAL priority states (HEAT, COOL, DEFROST, LOW_TEMP) are gated — blocked until the timer expires
    • LOW_TEMP has special handling: output protection (CNT/FAN/RV off, W management) is applied immediately, but the state label is deferred until validation completes
    • Dashboard shows a "State Hold" pill (blue) with countdown during validation
    • Configurable via heatpump.stateValidation.delayMs in config JSON (0–300 seconds, live)
  • Output State Validation — Every 10 seconds, validateOutputStates() verifies all relay outputs match the expected state for the current operating mode using a table-driven approach:

    • Global invariants enforced first: W must never be on when O is active; CNT must be off during any blocking fault (priority: compressor overtemp > suction low temp > LPS fault > low temp > RV fail)
    • Per-state table defines expected output values: OFF=all off, COOL=RV on/W off, HEAT=RV off, DEFROST Ph3=RV+W on/FAN off, ERROR=CNT off, LOW_TEMP=CNT+FAN+RV off
    • Transition phase rows validated: COOL Trans Ph1/Ph2, HEAT Trans Ph1/Ph2, DEFROST Ph1/Ph2, Defrost Exit Ph1/Ph2
    • Mismatches are logged as errors and auto-corrected
    • Skipped during startup lockout and manual override only (transitions are now validated)
    • Manual override also bypasses the state validation timer so it doesn't interfere with manual pin control testing
    • Logs "State check OK" at info level every 30 seconds when all outputs are correct
  • Adaptive Defrost Bands — Colder ambient temperatures cause faster ice buildup on the outdoor coil, requiring more frequent defrost cycles. Instead of a single fixed runtime threshold, the controller uses 3 ambient temperature bands — each with its own heat runtime threshold, minimum defrost duration, and condenser exit temperature:

    Band Ambient Range Runtime Threshold Min Defrost Condenser Exit Temp
    Cold ≤ 23°F 30 min 2 min 50°F
    Mid 23–31°F 60 min 1.5 min 55°F
    Warm ≥ 31°F 90 min 1 min 60°F

    All values are configurable via the config page "Defrost Bands" fieldset. The two breakpoint temperatures (coldMaxTemp, warmMinTemp) define the band boundaries and can be adjusted independently.

    How it works:

    • The active band is selected every update cycle based on the current ambient temperature (using the same 3-tier fallback: sensor → weather → ESP32 internal temp)
    • When no ambient data is available, the system defaults to the Warm band (most conservative — longest runtime before defrost triggers)
    • When defrost starts, the active band's parameters are snapshotted and frozen for the duration of the cycle. If ambient temperature drifts mid-defrost (e.g., the sun comes up), the exit criteria stay stable — no mid-cycle parameter jumps
    • Dashboard and OLED display show the current band and progress: Heat RT: 42m / 60m (Mid)
    • /state JSON includes defrostBand (active band name) and defrostBandThresholdMin (active threshold in minutes)

    Config JSON structure:

    "defrost": {
        "active": false,
        "coldMaxTemp": 23.0,
        "warmMinTemp": 31.0,
        "cold": { "runtimeThresholdMs": 1800000, "minRuntimeMs": 120000, "exitTempF": 50.0 },
        "mid":  { "runtimeThresholdMs": 3600000, "minRuntimeMs": 90000,  "exitTempF": 55.0 },
        "warm": { "runtimeThresholdMs": 5400000, "minRuntimeMs": 60000,  "exitTempF": 60.0 }
    }

    Backward compatibility: Devices upgrading from firmware with single-value defrost settings (heatRuntimeThresholdMs, minRuntimeMs, exitTempF) auto-migrate on first config load. The old values become the Warm band, and Mid/Cold bands are derived proportionally. Old keys are removed on the next config save.

  • Automatic Defrost (3-Phase Sequencing) — After the active band's heat runtime threshold of accumulated CNT runtime in HEAT mode while DFT is active (coil temp ≤ 32°F, indicating icing conditions), initiates a 3-phase software defrost cycle for safe pressure equalization and output sequencing:

    Phase 1 — Pressure Equalization (defrostTransition):

    • All outputs OFF (CNT, FAN, W, RV)
    • Duration: heatpump.shortCycle.rv (default 30s)
    • Allows system pressures to equalize before reversing valve switches

    Phase 2 — RV + W Engaged, CNT Hold (defrostCntPending):

    • RV and W turned ON, CNT remains OFF
    • Duration: heatpump.shortCycle.cnt (default 30s)
    • Allows reversing valve to fully seat before compressor starts

    Phase 3 — Active Defrost:

    • CNT turned ON, defrost fully active
    • Runs for at least the active band's minimum defrost time before checking exit conditions
    • Rechecks CONDENSER_TEMP every 1 minute during defrost with logging
    • Exits when CONDENSER_TEMP >= the active band's exit temperature or 15-minute safety timeout
  • Defrost Exit Transition (3-Phase) — When defrost completes (condenser temp reached or timeout), the system performs a reverse 3-phase sequence to safely switch the reversing valve back to heat position before restarting the compressor:

    Exit Phase 1 — Pressure Equalization (defrostTransition + defrostExiting):

    • CNT, FAN, and W turned OFF immediately; RV stays ON
    • Duration: heatpump.shortCycle.rv (default 30s)
    • Allows system pressures to equalize after compressor stops

    Exit Phase 2 — RV Switch + CNT Hold (defrostCntPending + defrostExiting):

    • RV turned OFF (switches back to heat position), CNT remains OFF
    • Duration: heatpump.shortCycle.cnt (default 30s)
    • Allows reversing valve to physically seat before compressor restarts

    Exit Complete:

    • CNT and FAN turned ON — system resumes normal HEAT mode operation
    • State machine has already transitioned from DEFROST to HEAT at exit start

    Additional defrost behavior:

    • Heat runtime only accumulates when DFT input is active (closed at 32°F, indicating icing conditions)
    • DFT turning off (temps > 32°F) clears accumulated runtime after a 30-second debounce — prevents false resets from intermittent DFT wire contact
    • Only COOL and DEFROST modes clear accumulated runtime; Y going off does not
    • Only HEAT mode adds time to accumulated runtime
    • Runtime persists to SD card every 5 minutes, restored on boot
    • Y drop during defrost entry: All outputs turn off (including W), transition flags are cleared, but _softwareDefrost stays set. When Y reactivates in HEAT mode, defrost restarts from Phase 1
    • Y drop during defrost exit: All outputs turn off, exit transition cancelled. Normal state machine resumes on Y reactivation
    • COOL cancellation: If the thermostat switches to COOL mode (O becomes active) during any phase of a pending defrost, the defrost is cancelled entirely, heat runtime is cleared, and the system enters normal COOL mode
  • HEAT→COOL Mode Transition (3-Phase) — When switching from HEAT to COOL (O input activates), the reversing valve must switch safely with the compressor stopped:

    Phase 1 — Pressure Equalization (coolTransition):

    • CNT and FAN turned OFF, RV stays OFF (from HEAT position)
    • Duration: heatpump.shortCycle.rv (default 30s)

    Phase 2 — RV On + CNT Hold (coolCntPending):

    • RV turned ON (switches to COOL position), CNT remains OFF
    • Duration: heatpump.shortCycle.cnt (default 30s)

    Complete: CNT and FAN turned ON — normal COOL mode active. If RV is already ON (e.g., from defrost Phase 2/3→COOL), the transition is skipped.

  • COOL→HEAT Mode Transition (3-Phase) — When switching from COOL to HEAT (O input deactivates), the reversing valve must switch safely with the compressor stopped:

    Phase 1 — Pressure Equalization (heatTransition):

    • CNT and FAN turned OFF, RV stays ON (from COOL position)
    • Duration: heatpump.shortCycle.rv (default 30s)

    Phase 2 — RV Off + CNT Hold (heatCntPending):

    • RV turned OFF (switches to HEAT position), CNT remains OFF
    • Duration: heatpump.shortCycle.cnt (default 30s)

    Complete: CNT and FAN turned ON — normal HEAT mode active.

    Both mode transitions abort on Y drop or state change (fault/LOW_TEMP), turning all outputs off.

State Table

State Condition FAN CNT RV W Notes
OFF Y inactive OFF OFF OFF OFF All outputs off
HEAT Y active, O inactive ON ON OFF OFF CNT has 30s short-cycle protection
COOL Y active, O active ON ON ON OFF Will not operate below 20°F
DEFROST Phase 1 Pressure equalization (30s) OFF OFF OFF OFF All outputs off for pressure equalization
DEFROST Phase 2 RV + W engaged, CNT hold (30s) OFF OFF ON ON Reversing valve seats before compressor starts
DEFROST Phase 3 Active defrost OFF ON ON ON Band-specific min time/exit temp (see Adaptive Defrost Bands), 15-min safety timeout
HEAT Exit Phase 1 Defrost exit pressure equalization (30s) OFF OFF ON ON RV+W stay on from defrost, CNT+FAN off
HEAT Exit Phase 2 RV switch + CNT hold (30s) OFF OFF OFF OFF RV switches back to heat position
HEAT Exit Complete CNT+FAN resume ON ON OFF OFF Normal HEAT mode resumes
COOL Trans Phase 1 HEAT→COOL pressure equalization (30s) OFF OFF OFF OFF CNT+FAN off before RV switches
COOL Trans Phase 2 RV on, CNT hold (30s) OFF OFF ON OFF RV seats before compressor starts
HEAT Trans Phase 1 COOL→HEAT pressure equalization (30s) OFF OFF ON OFF CNT+FAN off, RV still on from COOL
HEAT Trans Phase 2 RV off, CNT hold (30s) OFF OFF OFF OFF RV switches to HEAT position
ERROR LPS fault (low pressure) OFF OFF OFF ON* *W on only in HEAT mode (Y active, O inactive)
LOW_TEMP Ambient < 20°F OFF OFF OFF ON* *W on only in HEAT mode; W turns off if thermostat switches to COOL (Y+O)
HEAT + RV Fail RV fail latched ON OFF OFF ON* *W on only in HEAT mode; CNT blocked until cleared

Fault Conditions (overlay on current state, block CNT activation):

Fault Condition Trigger Recovery FAN CNT W Priority
Compressor overtemp COMPRESSOR_TEMP ≥ 240°F Any mode Temp < 190°F ON OFF OFF 1 (highest)
Suction low temp SUCTION_TEMP < 32°F COOL mode only Temp > 40°F ON OFF OFF 2
LPS fault LPS input LOW Any mode LPS goes HIGH OFF OFF ON* 3
Low ambient temp AMBIENT_TEMP < 20°F for 10 min Any mode Temp ≥ 20°F for 10 min OFF OFF ON* 4
RV fail SUCTION_TEMP ≥ 140°F during defrost Defrost only Manual clear via dashboard/config ON OFF ON* Latched

* W on only in HEAT mode (Y active, O inactive); never activated in COOL mode (Y+O).

Fault Priority: Compressor overtemp > Suction low temp > LPS fault > Low ambient temp. Higher-priority faults take precedence; lower-priority checks are skipped while a higher-priority fault is active.

Class Structure

Class Purpose
GoodmanHP Central controller with pin maps, temp sensors, and state machine
InputPin Digital/analog input with polling-based validation delay, confirmed-state debouncing, callbacks
OutPin Output relay with delay, PWM support, state tracking, hardware state validation
TempSensor Temperature sensor with callbacks; supports OneWire (DS18B20), I2C (MCP9600), and SPI (MAX6675). 6 default names: COMPRESSOR, SUCTION, AMBIENT, CONDENSER, LIQUID, VAPOR
Config SD card and JSON configuration management
Logger Multi-output logging with tar.gz rotation, ring buffer, and WebSocket streaming
WebHandler AsyncWebServer (port 80) with REST API, WebSocket, and HTTPS redirects
HttpsServer ESP-IDF HTTPS server (port 443) for secure endpoints
MQTTHandler MQTT client with auto-reconnect and topic publishing

Hardware

Supported boards:

  • Freenove ESP32-S3-WROOM (primary)
  • ESP32 DevKit

GPIO Pin Mapping (ESP32-S3):

Pin GPIO Direction Description
LPS 15 Input Low Pressure Switch
DFT 16 Input Defrost signal
Y 17 Input Compressor request (heat or cool)
O 18 Input Reversing valve signal (cool mode)
FAN 4 Output Fan relay
CNT 5 Output Contactor relay (3s delay)
W 6 Output Heating relay
RV 7 Output Reversing valve relay
SDA 8 I/O I2C data
SCL 9 I/O I2C clock
OneWire 21 I/O Temperature sensor bus
MAX6675 CLK 39 Output SPI thermocouple clock (software SPI)
MAX6675 CS 40 Output SPI thermocouple chip select
MAX6675 DO 41 Input SPI thermocouple data out
CAN TX 38 Output CAN bus transmit (TWAI)
CAN RX 14 Input CAN bus receive (TWAI)

I2C Devices:

Device Address Description
MCP9600 0x67 Type-K thermocouple amplifier (LIQUID_TEMP)
SSD1306 0x3C 128x64 OLED display (5-page auto-cycling status)

SPI Devices (software SPI):

Device Description
MAX6675 Type-K thermocouple reader for LIQUID_TEMP (highest priority in auto-detection)

MAX6675 Thermocouple Board Mounting:

The MAX6675 breakout board (32mm x 16mm) mounts to the inner ceiling of the top shell enclosure via a single M3 screw pillar. The terminal block protrudes through a rectangular cutout in the top shell.

  • Mounting pillar: 6mm OD, 6mm tall, M3 tap hole (2.5mm), attached to inner ceiling
  • Pillar position: 35mm from left outer edge, 28mm from top outer edge, offset 2mm toward bottom of board from center
  • Terminal cutout: 16mm x 14mm rectangular hole through the top shell at the top end of the board
  • Countersink: Shell thinned from 3mm to 1.5mm around the terminal opening, extending to the outer top edge for terminal block clearance
  • Default SPI pins: CLK=GPIO 39 (TCK), CS=GPIO 40 (TDO), DO=GPIO 41 (TDI) — freed JTAG header pins on ESP32-S3
  • 3D shell files: Located in shell/ — originals (3mm walls) and modified versions (3.5mm walls, flipped mating profile). See 3D Printed Shell section below

3D Printed Shell

The enclosure is an EasyEDA-exported 3D shell, post-processed with FreeCAD Python scripts for thicker walls, a flipped mating profile, and mounting hardware. All files are in the shell/ directory.

Shell files:

File Description
3DShell_GoodmanHPv3_T_3mm_TC.step/.stl Original top shell (3mm walls, tongue on outer half, TC mount)
3DShell_GoodmanHPv3_B_3mm.step/.stl Original bottom shell (3mm walls, groove on outer half)
3DShell_GoodmanHPv3_T_3.5mm_TC_flipped.step/.stl Modified top shell (3.5mm walls, groove replaces tongue)
3DShell_GoodmanHPv3_B_3.5mm_flipped.step/.stl Modified bottom shell (3.5mm walls, tongue replaces groove)
modify_top.py FreeCAD script to generate the modified top shell
modify_bottom.py FreeCAD script to generate the modified bottom shell
cutout.py Reusable FreeCAD utility library for cutout, standoff, and mounting operations

Why the mating profile was flipped: The original design had a tongue (raised band) on the top shell mating rim. When 3D printed, this thin horizontal band is prone to layer separation because it prints as an unsupported overhang at the shell's open edge. Moving the tongue to the bottom shell and the groove to the top eliminates this — the bottom tongue prints vertically up from the floor (strong layer adhesion), and the top groove is simply a recess in a solid wall.

Modifications applied:

  1. Wall thickening (3mm to 3.5mm) — 0.5mm added to the outer face of all 4 walls. Inner cavity dimensions unchanged so the PCB still fits. Wall cutouts (connector openings on right and back walls) are preserved by pre-cutting matching holes in the thickening ring before fusing.

  2. Mating profile flip — The rabbet/step joint between shells was inverted:

    • Bottom: Original groove (Z=31-35) filled, new outer tongue added with 0.10mm clearance per side
    • Top: Original tongue (Z=28-32) removed, new inner lip + outer groove cut
  3. M3 screw pillar — 5mm OD, 3mm tall pillar on the top shell ceiling for mounting the MAX6675 thermocouple board, with M3 (2.5mm) through-hole centered in the pillar

Utility library (cutout.py):

Composable functions for shell modifications. Each takes a Part.Shape and returns a modified shape. OCCT boolean operation quirks (oversized plugs, Z range matching, flush trimming) are handled internally:

Function Purpose
rectangular_cutout() Cut a window through a Z-normal surface
reposition_cutout() Plug an existing cutout and re-cut at a new position (3-step: oversized plug, matching-Z cut, flush trim)
add_standoff() Fuse a cylindrical pillar onto a surface (with auto-trim for reliable OCCT fuse)
drill_hole() Vertical through-hole along Z axis
drill_hole_lateral() Horizontal through-hole along X or Y axis (screw holes through walls)
add_standoffs_with_holes() Multiple standoffs + centered screw holes (convenience combo)
wall_ring() Rectangular ring (outer box minus inner box) for wall thickening and mating profiles
z_probe() Probe Z intersections at an XY point (verification)
verify_cutout() Check a rectangular cutout is fully open (probes center + corners)
verify_solid() Check material exists at a point between two Z levels

Example usage:

from cutout import reposition_cutout, add_standoff, drill_hole

# Reposition an LCD cutout (plug old hole, cut new, trim flush — all in one call)
result = reposition_cutout(result,
    old_x1=-38.48, old_y1=59.59, old_x2=-11.43, old_y2=76.59,
    new_x1=-38.48, new_y1=61.59, new_x2=-11.43, new_y2=77.59,
    z_inner=48.50, z_outer=51.50)

# Add a mounting standoff below the ceiling
result = add_standoff(result, cx=-63.76, cy=67.14,
    z_surface=48.50, height=3.0, radius=2.5, z_outer=51.50)

# Drill a screw hole through the standoff
result = drill_hole(result, cx=-63.76, cy=67.14,
    z_bottom=45.50, z_top=51.50, radius=1.25)

Regenerating modified shells:

# Requires FreeCAD installed (sudo apt install freecad)
freecadcmd shell/modify_top.py
freecadcmd shell/modify_bottom.py

Key geometry constants (all in mm, origin at EasyEDA export origin):

Constant Value Description
Outer walls X[-98.26, 4.92] Y[-32.48, 97.12] Original 3mm outer face
Inner walls X[-95.26, 1.92] Y[-29.48, 94.12] Original 3mm inner face
New outer X[-98.76, 5.42] Y[-32.98, 97.62] After 0.5mm thickening
Bottom mating zone Z=31 to Z=35 Groove (original) / Tongue (modified)
Top mating zone Z=28 to Z=32 Tongue (original) / Groove (modified)
Right wall cutout Y[47, 88.5] Z[7, 24] Connector opening, +X wall
Back wall lower cutout X[-50, -35] Z[6, 13] Opening, +Y wall
Back wall upper cutout X[-89.5, -3.5] Z[14, 17] Opening, +Y wall

Modifying EasyEDA 3D Shell Exports with Claude Code

EasyEDA exports PCB enclosures as STEP files with thin walls (typically 1.5mm). These often need post-processing — thicker walls, mating features, mounting hardware, cutouts — which can be done programmatically via FreeCAD's Python API and Claude Code. Below is a reusable prompt template and the key lessons learned from this project's shell modifications.

Prerequisites: freecad package installed (sudo apt install freecad), STEP files exported from EasyEDA's 3D shell generator.

Prompt template — adapt the bracketed sections to your project:

I have EasyEDA-exported STEP enclosure shells at [path/to/shells/]:

  • [Bottom_Shell.step] — bottom half, open top
  • [Top_Shell.step] — top half, open bottom

The shells have [1.5mm] walls. I need the following modifications:

  1. Wall thickening — Increase wall thickness from [1.5mm] to [3mm] by expanding outward. Keep inner cavity dimensions identical to the original so the PCB still fits. Preserve all interior features (screw pillars, standoffs, alignment posts) from the original STEP by extracting them via boolean intersection and fusing them back into the thickened shell.

  2. Mating joint — Add a rabbet/step joint between top and bottom shells in the overlap zone where both rims meet:

    • Bottom: remove outer half of wall for [4mm] from the rim (groove)
    • Top: remove inner half of wall in the overlap zone + add outer-half tongue extending [4mm] below the rim with [0.2mm] clearance
    • The tongue must overlap at least [2mm] into existing wall geometry above the rim for OCCT fuse to succeed (coincident-face workaround)
  3. Screw holes — Drill [M1.2] through-holes at [left and right wall midpoints], centered in the interlocking overlap zone so the screw passes through both the tongue and groove lip

  4. Cutouts — Cut rectangular openings in the top shell for: [LCD window at X1,Y1 to X2,Y2], [wire pass-through at ...], [connector at ...]

  5. Mounting features — Add a screw pillar on the inner ceiling of the top shell at [position] for mounting a [component]. [Xmm] OD, [Xmm] tall, [MX] tap hole

Write a FreeCAD Python script (freecadcmd script.py) that loads the STEP files, performs all modifications via boolean operations, and exports both STL and STEP. Include a verification section that cross-sections the results and prints geometry at key Z levels.

Key lessons for FreeCAD/OCCT boolean operations:

Issue Symptom Fix
Coincident face fuse failure fuse() adds volume but geometry doesn't extend beyond shared face Extend the new body 1-2mm past the shared face into existing solid so they overlap, not just touch
makeOffsetShape fails on complex shells Exception or degenerate result Rebuild parametrically: create outer box, cut inner cavity, extract+fuse interior features from original via common()
Thickening shifts features Mounting tabs, screw pillars stay at original positions After thickening, extract features by region (common() with probe box), translated() to correct position, cut old + fuse shifted
Groove/tongue on wrong wall half Joint doesn't interlock — both pieces occupy same space Groove removes outer half; tongue occupies outer half (filling the groove space). Cut inner half of mating shell in overlap zone so it nests with the other shell's remaining inner lip
removeSplitter() drops geometry Thin or newly-fused features disappear Check volume before/after; if features vanish, skip removeSplitter() or increase overlap
STEP export loses thin features Feature exists in memory (volume correct) but missing after reload Ensure minimum 0.5mm thickness on all features; export STL as backup (mesh-based, more tolerant)

Verification pattern — always include in your script:

# Cross-section at key Z levels to verify wall profiles
for z in [key_z_values]:
    plane = Part.makePlane(250, 200, Vector(-150, -100, z), Vector(0, 0, 1))
    sec = shape.section(plane)
    sbb = sec.BoundBox
    print(f"Z={z}: X[{sbb.XMin:.2f},{sbb.XMax:.2f}] Y[{sbb.YMin:.2f},{sbb.YMax:.2f}]")

Typical workflow:

  1. Analyze — Load STEP, print bounding boxes, cross-section at rim levels to get exact wall coordinates (outer, inner, midpoint)
  2. Thicken — Parametric rebuild with makeBox + cut (more reliable than makeOffsetShape on EasyEDA exports)
  3. Interior featuresoriginal.common(cavity_box) extracts pillars/standoffs, fuse() them into new shell
  4. Mating edge — Groove (cut outer half) + tongue (fuse outer half extension with 2mm overlap into wall) + step (cut inner half in overlap zone)
  5. Hardware — Screw holes (makeCylinder + cut), mounting pillars (makeCylinder + fuse), cutouts (makeBox + cut)
  6. Export.exportStep() for CAD, MeshPart.meshFromShape() + .write() for STL printing

Getting Started

Prerequisites

  • PlatformIO (CLI or IDE extension)
  • USB cable connected to ESP32 board

Linux/macOS: Shell scripts in scripts/ (.sh) require bash and curl.

Windows: PowerShell scripts in scripts/ (.ps1) require PowerShell 5.1+ (included with Windows 10/11) and curl.exe (included with Windows 10+). Some scripts also require openssl (included with Git for Windows). Run with: powershell -ExecutionPolicy Bypass -File .\scripts\<script>.ps1

Secrets Setup

Create secrets.ini in the project root (gitignored — never committed):

[secrets]
build_flags =
	-D XOR_KEY=\"your-random-base64-key\"

XOR_KEY is used as a fallback key for password encryption on the SD card when no eFuse HMAC key is provisioned (see Password Encryption). Generate a random key with: openssl rand -base64 32

AP mode password is configured from the config page (wifi.apPassword in config JSON) or auto-generated randomly at runtime if not set. It is no longer a build-time constant.

Build and Upload

PlatformIO commands work the same on all platforms:

# Build
pio run -e freenove_esp32_s3_wroom

# Upload firmware
pio run -t upload -e freenove_esp32_s3_wroom

# Serial monitor
pio run -t monitor -e freenove_esp32_s3_wroom

On Linux, if pio is not on PATH, use ~/.platformio/penv/bin/pio. On Windows, use %USERPROFILE%\.platformio\penv\Scripts\pio.exe.

SD Card Setup

The SD card should contain:

/config.txt              — Device configuration (WiFi, MQTT, sensors, admin password)
/www/index.html          — Home page
/www/dashboard.html      — Live dashboard with charts
/www/pins.html           — Pin table with manual override
/www/config.html         — Configuration page
/www/update.html         — OTA update page
/www/log.html            — Log viewer
/www/heap.html           — System/heap info
/www/wifi.html           — WiFi scan and setup
/www/theme.css           — Shared dark/light theme stylesheet
/cert.pem                — HTTPS certificate (optional, see below)
/key.pem                 — HTTPS private key (optional, see below)
/temps/<sensor>/*.csv    — Temperature history CSVs (auto-created)

Generate config.txt interactively:

# Linux/macOS
./scripts/configure.sh --local

# Windows (PowerShell)
.\scripts\configure.ps1 -Local

This prompts for system name, MQTT prefix, WiFi, and MQTT credentials, then writes data/config.txt. Copy it to the SD card root. Passwords are stored in plaintext and encrypted automatically on first boot.

Manual config.txt format:

{
  "project": "Goodman",
  "created": "Feb 06 2026",
  "description": "Goodman heatpump controller",
  "system": {
    "name": "Goodman HP",
    "mqttPrefix": "goodman"
  },
  "wifi": {
    "ssid": "your-ssid",
    "password": "your-password"
  },
  "mqtt": {
    "user": "mqtt-user",
    "password": "mqtt-password",
    "host": "192.168.0.46",
    "port": 1883
  },
  "logging": {
    "maxLogSize": 52428800,
    "maxOldLogCount": 10
  },
  "runtime": {
    "heatAccumulatedMs": 0
  },
  "timezone": {
    "gmtOffset": -21600,
    "daylightOffset": 3600
  },
  "heatpump": {
    "lowTemp": { "threshold": 20.0 },
    "highSuctionTemp": { "threshold": 140.0, "rvFail": false },
    "shortCycle": { "rv": 30000, "cnt": 30000 },
    "defrost": { "minRuntimeMs": 180000, "exitTempF": 60.0, "heatRuntimeThresholdMs": 5400000 }
  },
  "tempHistory": {
    "intervalSec": 120
  },
  "ui": {
    "theme": "dark"
  },
  "admin": {
    "password": "",
    "ftpPassword": ""
  },
  "sensors": {
    "temp": {
      "288514B2000000EA": { "description": "AMBIENT_TEMP", "name": "AMBIENT_TEMP" },
      "28C7E8B200000076": { "description": "CONDENSER_TEMP", "name": "CONDENSER_TEMP" },
      "28DCC0B200000013": { "description": "COMPRESSOR_TEMP", "name": "COMPRESSOR_TEMP" },
      "2862D5B2000000A9": { "description": "SUCTION_TEMP", "name": "SUCTION_TEMP" }
    },
    "max6675": { "clk": 39, "cs": 40, "do": 41, "enabled": true }
  }
}

Configuration options:

  • system.name — System display name, max 20 characters, alphanumeric + spaces (default: "Goodman HP"). Used as web UI brand, AP SSID, OLED display name, HTTPS auth realm, and SSL certificate CN. Requires reboot
  • system.mqttPrefix — MQTT topic prefix (default: "goodman"). Topics become <prefix>/temps, <prefix>/state, <prefix>/fault, <prefix>/log. Requires reboot
  • logging.maxLogSize — Maximum log file size in bytes before rotation (default: 52428800 = 50MB)
  • logging.maxOldLogCount — Number of rotated log files to keep (default: 10)
  • tempHistory.intervalSec — Temperature history capture interval in seconds, 30-300 (default: 120)
  • heatpump.lowTemp.threshold — Ambient temp (°F) below which compressor is blocked (default: 20.0)
  • heatpump.highSuctionTemp.threshold — Suction temp (°F) above which RV fail is detected during defrost (default: 140.0)
  • heatpump.shortCycle.rv — Phase 1 pressure equalization delay in ms (default: 30000)
  • heatpump.shortCycle.cnt — Phase 2 CNT short cycle delay in ms (default: 30000)
  • heatpump.stateValidation.delayMs — State validation hold time in ms after state changes; prevents rapid cycling (default: 30000 = 30s, range: 0–300s, live)
  • heatpump.inputDelay.ms — Input pin validation delay in ms; re-reads GPIO after delay to confirm state change (default: 2000 = 2s, range: 0–60s, live)
  • heatpump.defrost.minRuntimeMs — Minimum Phase 3 runtime in ms before checking exit conditions (default: 180000 = 3 min)
  • heatpump.defrost.exitTempF — Condenser temp (°F) at which Phase 3 exits (default: 60.0)
  • heatpump.defrost.heatRuntimeThresholdMs — Accumulated HEAT runtime in ms before triggering defrost (default: 5400000 = 90 min, range: 1–90 min via config page)
  • sensors.max6675.clk — MAX6675 SPI clock pin (default: 39, requires reboot)
  • sensors.max6675.cs — MAX6675 SPI chip select pin (default: 40, requires reboot)
  • sensors.max6675.do — MAX6675 SPI data out pin (default: 41, requires reboot)
  • sensors.max6675.enabled — Enable MAX6675 thermocouple sensor (default: true, requires reboot)

Log file rotation:

  • Active log: /log.txt (uncompressed)
  • Rotated logs: /log.1.tar.gz, /log.2.tar.gz, ... /log.N.tar.gz (compressed)
  • When /log.txt exceeds maxLogSize, it is compressed and rotated
  • Oldest log is deleted when count exceeds maxOldLogCount
  • Falls back to .txt extension if compression fails

In-memory log ring buffer:

  • Stores the last 500 log entries in PSRAM for fast retrieval
  • Access via GET /log — returns all entries as JSON
  • Use GET /log?limit=N to return only the last N entries
  • Response format:
    {"count": 42, "entries": ["[2026/02/10 14:32:01] [INFO ] [HP] State changed", "..."]}

WebSocket log streaming:

  • All log entries are broadcast to connected /ws clients in real-time
  • Message format: {"type":"log","message":"[2026/02/10 14:32:01] [INFO ] [HP] ..."}
  • Enabled by default; toggle via POST /log/config?websocket=true|false

Temperature history CSV logging:

  • Logs all 6 temperature sensors (ambient, compressor, suction, condenser, liquid, vapor) at a configurable interval (30s-5min, default 2min)
  • Per-sensor CSV files: /temps/<sensor>/YYYY-MM-DD.csv (e.g., /temps/ambient/2026-02-11.csv)
  • CSV format (no header): epoch_seconds,temperature_fahrenheit
  • ~56 KB/day per sensor, ~10 MB/month total across all 6 sensors
  • Auto-purges CSV files older than 31 days
  • Access via GET /temps/history?sensor=<name> API endpoint

Sensor addresses are discovered automatically on startup and can be mapped to names via this config.

HTTPS / SSL

The device runs a secondary HTTPS server (ESP-IDF esp_https_server) on port 443 for sensitive endpoints (/config, /update, /ftp). The AsyncWebServer on port 80 redirects those paths to HTTPS.

Generate a self-signed certificate:

# Linux/macOS
./scripts/generate-cert.sh                    # CN=ESP32 (default)
./scripts/generate-cert.sh "My Heatpump"      # CN=My Heatpump

# Windows (PowerShell)
.\scripts\generate-cert.ps1                    # CN=ESP32 (default)
.\scripts\generate-cert.ps1 -Name "My Heatpump"

This creates cert.pem and key.pem (ECC P-256, 10-year validity). The CN (Common Name) defaults to "ESP32" but can be set to match the system name. Copy both files to the SD card root. If no certificates are found, all endpoints fall back to HTTP. The device also auto-generates a self-signed certificate on boot if none are found on the SD card, using the configured system name as the CN.

Admin Password

Sensitive endpoints (/config, /update, /ftp) are protected by HTTP Basic Auth when an admin password is set.

  • No password set — All endpoints are open, no authentication required
  • Password set — Browser prompts for Basic Auth (username: admin, password: your admin password)
  • Set the admin password from the config page (/config) or via the API
  • Setting a password automatically disables FTP if it was running

Password Encryption

All passwords (WiFi, MQTT, admin, FTP) are encrypted at rest on the SD card using AES-256-GCM when a hardware HMAC key is provisioned, or XOR obfuscation as a fallback. Plaintext passwords are automatically encrypted on the next config save.

Encryption tiers:

Tier Method Key Source Prefix Security
1 (recommended) AES-256-GCM eFuse HMAC hardware key $AES$ Key never leaves silicon — only the HMAC peripheral can access it. Cannot be extracted even with physical access to the flash/SD card
2 (fallback) XOR obfuscation XOR_KEY from secrets.ini $ENC$ Symmetric key compiled into firmware — extractable from firmware binary
3 (no key) Plaintext None (none) No encryption — passwords readable on SD card

How it works: On boot, the firmware calls esp_hmac_calculate() with eFuse BLOCK_KEY0 and a salt to derive a 256-bit AES key. The eFuse key is read-protected (-/-) — software cannot read it directly; only the ESP32-S3 hardware HMAC peripheral can use it to produce derived keys. Each password is encrypted with a unique random 12-byte IV (nonce), and the GCM authentication tag ensures tampering is detected.

Provisioning the eFuse HMAC key:

# Linux/macOS
./scripts/burn-efuse-key.sh [/dev/ttyUSB0]

# Windows (PowerShell)
.\scripts\burn-efuse-key.ps1 [-Port COM3]

This permanently burns a random 256-bit HMAC key to eFuse BLOCK_KEY0 with HMAC_UP purpose. The key block becomes read-protected and write-protected immediately after burning.

WARNING: eFuse burning is permanent and irreversible. Each key block can only be written once per chip. A backup of the key is saved to efuse_hmac_key.bin (gitignored) — store this securely.

Verified on hardware (2026-02-22):

$ espefuse.py summary (before burn)
BLOCK_KEY0: Purpose=USER, Access=R/W, Data=00 00 00 ... 00

$ espefuse.py burn_key BLOCK_KEY0 efuse_hmac_key.bin HMAC_UP
BURN BLOCK4 - OK
BURN BLOCK0 - OK

$ espefuse.py summary (after burn)
BLOCK_KEY0: Purpose=HMAC_UP, Access=-/-, Data=?? ?? ?? ... ??

Boot log:
  AES-256-GCM encryption enabled (eFuse HMAC key found)
  Admin password encryption: $AES$
  Admin password: set

Existing $ENC$ passwords are automatically re-encrypted as $AES$ on the next config save. The firmware handles all three tiers transparently — it decrypts any format and re-encrypts with the highest available tier on save.

FTP Server

FTP (SimpleFTPServer on port 21) is used for uploading HTML files to the SD card's /www/ directory.

  • FTP defaults to OFF at boot
  • Enabling/disabling FTP requires admin authentication (via /ftp API endpoint)
  • Enable from the config page with timed durations (10/30/60 min), auto-disables after timeout
  • FTP password is configurable from the config page. Stored encrypted ($AES$/$ENC$) in admin.ftpPassword in config JSON. When not set, defaults to admin. Username is always admin
  • The /ftp GET status endpoint includes the active password in its response, allowing scripts to auto-detect the configured password
  • Max password length: 16 characters (SimpleFTPServer FTP_CRED_SIZE limit)

Upload web pages via HTTPS:

# Linux/macOS
./scripts/update-www.sh                          # Upload all files
./scripts/update-www.sh dashboard.html           # Upload a single file
./scripts/update-www.sh --usb [port]             # Flash via USB serial

# Windows (PowerShell)
.\scripts\update-www.ps1                          # Upload all files
.\scripts\update-www.ps1 -File dashboard.html     # Upload a single file
.\scripts\update-www.ps1 -USB [-Port COM3]        # Flash via USB serial

This script prompts for the device IP and admin password, then uploads files from data/www/ to the device's LittleFS /www/ directory via HTTPS.

WiFi AP Fallback

If the device cannot connect to WiFi for a configurable timeout (default 10 minutes), it automatically switches to Access Point (AP) mode for emergency OTA updates and configuration changes.

  • SSID: Configured system name (default: Goodman HP). Set via config page or system.name in config JSON
  • Password: Random 8-character alphanumeric, generated fresh on each AP activation. Displayed on the OLED screen and logged to serial
  • IP: 192.168.4.1
  • All web endpoints work in AP mode (dashboard, config, OTA update, log, heap)
  • HTTPS is not available in AP mode — use HTTP (http://192.168.4.1)
  • OLED display shows AP credentials (SSID, password, IP) and holds the screen 3x longer for readability
  • The device automatically attempts to reconnect to the configured WiFi every 60 seconds while in AP mode
  • AP mode ends automatically when WiFi reconnects, or persists until reboot

Recovery workflow:

  1. Check the OLED display or serial log for the AP SSID and password
  2. Connect to the AP WiFi network
  3. Browse to http://192.168.4.1/config to fix WiFi credentials
  4. Or upload new firmware via http://192.168.4.1/update
  5. The device will reconnect to WiFi automatically when credentials are corrected, or reboot to force reconnection

Crash Recovery

The device has multiple layers of crash recovery to prevent unrecoverable states in the field.

Boot Watchdog / Safe Mode

An RTC_NOINIT_ATTR crash counter persists across software resets (cleared only on power-on). Each PANIC, INT_WDT, TASK_WDT, or WDT reset increments the counter. If it reaches 3 consecutive crash boots, the device enters safe mode automatically.

Safe mode behavior:

  • Heat pump controller is fully disabled (no I/O pins, no state machine, no relay control)
  • WiFi, web server, configuration, FTP, logging, CPU monitoring, and OLED display remain operational
  • The OLED display shows ** SAFE MODE ** on the boot screen and protections page
  • /state JSON includes safeMode: true, crashBootCount, and resetReason
  • A 30-second stable boot timer resets the crash counter, so a single successful boot clears the history

Forcing safe mode: POST /safemode/force sets a one-shot config flag (safeMode.force in config JSON) that triggers safe mode on the next boot. The flag is automatically cleared after entering safe mode so subsequent boots are normal. Useful for maintenance or debugging.

Clearing safe mode: POST /safemode/clear clears the force flag and reboots.

Automatic Firmware Revert

When the device enters safe mode due to a crash boot loop (3+ consecutive crash resets) and a firmware backup exists on SD card (/firmware.bak), the boot watchdog automatically attempts to revert to the previous firmware.

Build date verification: Each OTA apply operation saves the running firmware's build date to /firmware.bak.meta alongside the binary backup. Before reverting, the watchdog compares the backup's build date against the currently running firmware. If they match, the backup is the same build as the crashing firmware — reverting would just re-flash the same broken code. In this case, the revert is skipped and the device continues in safe mode.

Scenario Backup exists Build dates Action
OTA update caused crash loop Yes Different Auto-reverts to backup, reboots
Same firmware crashing Yes Same Skips revert, stays in safe mode
No metadata file (legacy backup) Yes Unknown Attempts revert (benefit of the doubt)
USB upload caused crash loop No N/A No backup available, stays in safe mode

Why OTA is preferred over USB: OTA updates (POST /update + POST /apply) automatically back up the running firmware to /firmware.bak with build date metadata before flashing. If the new firmware causes a crash loop, the boot watchdog can revert automatically. USB flashing (pio run -t upload) bypasses this entirely — no backup is created, so auto-revert is not possible. Always prefer OTA for production deployments.

Reboot Rate Limiting

To prevent denial-of-service via the /reboot endpoint, the device tracks rapid software reboots using an RTC_NOINIT_ATTR counter (separate from the crash counter). After 3 rapid reboots within 5 minutes, further /reboot API calls return 429 Too Many Requests. The rate limit clears after 5 minutes of stable uptime.

Rate-limited reboot attempts are logged at [ERROR] [SEC] level with the client IP address and User-Agent header for forensic analysis.

Recovery Options Summary

Problem Recovery
Bad OTA firmware (crash loop) Automatic: boot watchdog reverts to /firmware.bak
Bad USB firmware (crash loop) Manual: enter safe mode (auto after 3 crashes), upload fixed firmware via web UI or OTA
Bad configuration Manual: force safe mode (POST /safemode/force), fix config via web UI
WiFi credentials wrong Automatic: AP fallback after 10 min, fix via http://192.168.4.1/config
Device unreachable Manual: power cycle, connect via AP mode, or USB serial
/reboot DoS attack Automatic: rate limited after 3 rapid reboots

Scripts

All scripts prompt interactively for required parameters (device IP, admin password, etc.). Each script has both a Linux/macOS (.sh) and Windows PowerShell (.ps1) version with identical functionality.

Linux/macOS Windows (PowerShell) Description
configure.sh [--local] configure.ps1 [-Local] Configure device credentials or generate local config.txt
ota-update.sh [--revert] ota-update.ps1 [-Revert] OTA firmware upload, verify, flash, reboot, or rollback
update-www.sh [file] [--usb] update-www.ps1 [-File name] [-USB] [-Port COM3] Upload web pages to device via HTTPS or USB serial
backup-config.sh backup-config.ps1 Download config.txt from device for local backup
restore-config.sh [file] restore-config.ps1 [-File path] Restore config.txt to device from a local backup
generate-cert.sh [name] generate-cert.ps1 [-Name "name"] Generate self-signed ECC P-256 cert for HTTPS
burn-efuse-key.sh [port] burn-efuse-key.ps1 [-Port COM3] Burn hardware encryption key to ESP32-S3 eFuse

Interactive prompts (where applicable): Device IP, Admin password, System name, MQTT prefix, WiFi/MQTT credentials, confirmation prompts. PowerShell scripts use masked input (Read-Host -AsSecureString) for all password prompts.

scripts/configure.sh / configure.ps1

Configure WiFi and MQTT credentials on the device or generate a local config file for SD card provisioning. System name is validated: alphanumeric + spaces only, max 20 characters, sanitized automatically if invalid characters are entered.

# Linux/macOS
./scripts/configure.sh           # Push config to device via HTTPS API
./scripts/configure.sh --local   # Generate data/config.txt for SD card

# Windows (PowerShell)
.\scripts\configure.ps1           # Push config to device via HTTPS API
.\scripts\configure.ps1 -Local    # Generate data\config.txt for SD card

Prompts (network mode): Device IP, Admin password, System Name, MQTT Topic Prefix, WiFi SSID, WiFi password, Current WiFi password (if changing), MQTT host/port/user, MQTT password, Current MQTT password (if changing)

Prompts (local mode): System Name, MQTT Topic Prefix, WiFi SSID, WiFi password, MQTT host/port/user, MQTT password

scripts/ota-update.sh / ota-update.ps1

OTA firmware update via HTTPS. Uploads the PlatformIO build output to the device SD card, verifies the upload size, applies (backs up current firmware + flashes new), and waits for reboot.

# Linux/macOS
./scripts/ota-update.sh           # Upload and flash firmware
./scripts/ota-update.sh --revert  # Roll back to previous firmware backup

# Windows (PowerShell)
.\scripts\ota-update.ps1           # Upload and flash firmware
.\scripts\ota-update.ps1 -Revert   # Roll back to previous firmware backup

Prompts: Device IP, Admin password

Requires: Built firmware at .pio/build/freenove_esp32_s3_wroom/firmware.bin

scripts/update-www.sh / update-www.ps1

Upload HTML files from data/www/ to the device LittleFS /www/ directory via HTTPS, or flash the entire LittleFS image via USB serial.

# Linux/macOS
./scripts/update-www.sh                    # Upload all files over HTTPS
./scripts/update-www.sh dashboard.html     # Upload a single file
./scripts/update-www.sh --usb [port]       # Flash via USB serial

# Windows (PowerShell)
.\scripts\update-www.ps1                    # Upload all files over HTTPS
.\scripts\update-www.ps1 -File dashboard.html
.\scripts\update-www.ps1 -USB [-Port COM3]  # Flash via USB serial

Prompts (HTTPS mode): Device IP, Admin password

scripts/backup-config.sh / backup-config.ps1

Download config.txt from the device SD card for local backup via FTP. Saves timestamped copies to backups/<YYYYMMDD-HHMMSS>/config.txt and a latest copy at backups/config-latest.txt. Automatically detects the configured FTP password from the device's /ftp status endpoint.

# Linux/macOS
./scripts/backup-config.sh

# Windows (PowerShell)
.\scripts\backup-config.ps1

Prompts: Device IP, Admin password

Note: The backups/ directory is gitignored since config files contain credentials.

scripts/restore-config.sh / restore-config.ps1

Restore a previously backed-up config.txt to the device SD card via FTP. Lists available backups for selection, validates JSON before uploading, verifies the upload size matches, and optionally reboots to load the new config. Automatically detects the configured FTP password from the device's /ftp status endpoint.

# Linux/macOS
./scripts/restore-config.sh                              # Pick from available backups
./scripts/restore-config.sh backups/config-latest.txt    # Restore a specific file

# Windows (PowerShell)
.\scripts\restore-config.ps1                              # Pick from available backups
.\scripts\restore-config.ps1 -File backups\config-latest.txt

Prompts: Backup selection (if no file specified), Device IP, Admin password, Reboot confirmation

scripts/generate-cert.sh / generate-cert.ps1

Generate a self-signed ECC P-256 certificate (10-year validity) for the ESP32 HTTPS server. Outputs cert.pem and key.pem to the project root. An optional system name parameter sets the certificate CN (Common Name).

# Linux/macOS
./scripts/generate-cert.sh                    # CN=ESP32 (default)
./scripts/generate-cert.sh "Goodman HP"       # CN=Goodman HP

# Windows (PowerShell)
.\scripts\generate-cert.ps1                    # CN=ESP32 (default)
.\scripts\generate-cert.ps1 -Name "Goodman HP"

No interactive prompts. Requires openssl (included with Git for Windows). Copy output files to SD card root.

scripts/burn-efuse-key.sh / burn-efuse-key.ps1

Burn a hardware encryption key to ESP32-S3 eFuse for password encryption at rest. The key is read-protected — only the hardware HMAC peripheral can access it.

# Linux/macOS
./scripts/burn-efuse-key.sh [/dev/ttyUSB0]

# Windows (PowerShell)
.\scripts\burn-efuse-key.ps1 [-Port COM3]

Parameters: Serial port (default: /dev/ttyUSB0 on Linux, COM3 on Windows)

Prompts: Two confirmation prompts (type yes, then BURN)

WARNING: eFuse burning is permanent and irreversible. Each key block can only be written once per chip. A backup of the key is saved to efuse_hmac_key.bin (gitignored).

API Endpoints

Method Path Auth Description
GET / Home page with clickable cards linking to each section (served from SD /www/index.html)
GET /dashboard Live dashboard with state, I/O, temps, and charts
GET /pins Yes Pin table page / JSON (?format=json) with manual override control
POST /pins Yes Toggle manual override, set output state, or force defrost (JSON body)
GET /state Full controller state as JSON (see below)
GET /temps Current temperature readings
GET /temps/history Temperature history CSV data (?sensor=<name>, optional &date=YYYY-MM-DD)
GET /heap Memory/heap statistics
GET /scan WiFi network scan
GET /log Recent log entries from ring buffer (?limit=N)
GET /log/level Current log level
POST /log/level Set log level
GET /log/config Logger output configuration
POST /log/config Configure logger outputs (serial, mqtt, sdcard, websocket)
GET /theme Current theme and system name ({"theme":"dark","systemName":"Goodman HP"})
GET /theme.css Shared dark/light theme CSS stylesheet
GET /i2c/scan Scan I2C bus for connected devices
GET /config Yes Configuration page / JSON (?format=json)
POST /config Yes Update configuration (JSON body)
GET /update Yes OTA firmware update page
POST /update Yes Upload new firmware (saved to SD as /firmware.new)
GET /apply Yes Check if uploaded firmware exists ({"exists":bool,"size":N})
POST /apply Yes Flash firmware from /firmware.new, reboots on success
GET /revert Yes Check if firmware backup exists ({"exists":bool,"size":N})
POST /revert Yes Revert to previous firmware from SD backup, reboots on success
POST /reboot Yes Reboot the device (2s delay). Rate limited: returns 429 after 3 rapid reboots
POST /safemode/force Yes Force safe mode on next boot (one-shot flag, cleared after entering safe mode)
POST /safemode/clear Yes Clear forced safe mode flag and reboot
GET /ftp Yes FTP server status ({"active":bool,"remainingMinutes":N,"password":"..."})
POST /ftp Yes Enable/disable FTP ({"duration":N} minutes, 0=off)
WS /ws WebSocket for real-time data and log streaming

Auth = Requires HTTP Basic Auth when admin password is set. Endpoints marked with "Yes" redirect to HTTPS (port 443) when SSL certificates are available.

GET /state

Returns the full controller state as JSON. Used by the dashboard for real-time polling.

{
  "state": "HEAT",
  "inputs": { "LPS": true, "DFT": false, "Y": true, "O": false },
  "outputs": { "FAN": true, "CNT": true, "W": false, "RV": false },
  "heatRuntimeMin": 42,
  "defrost": false,
  "lpsFault": false,
  "lowTemp": false,
  "compressorOverTemp": false,
  "suctionLowTemp": false,
  "startupLockout": false,
  "startupLockoutRemainSec": 0,
  "shortCycleProtection": false,
  "rvFail": false,
  "highSuctionTemp": false,
  "defrostTransition": false,
  "defrostTransitionRemainSec": 0,
  "defrostCntPending": false,
  "defrostCntPendingRemainSec": 0,
  "defrostExiting": false,
  "stateValidating": false,
  "stateValidationRemainSec": 0,
  "manualOverride": false,
  "manualOverrideRemainSec": 0,
  "temps": { "AMBIENT_TEMP": 48.1, "COMPRESSOR_TEMP": 72.5, "SUCTION_TEMP": 65.2, "CONDENSER_TEMP": 38.7, "LIQUID_TEMP": 185.3, "VAPOR_TEMP": 52.0 },
  "subcoolingF": -146.6,
  "cpuLoad0": 23,
  "cpuLoad1": 50,
  "freeHeap": 159232,
  "wifiSSID": "your-ssid",
  "wifiRSSI": -48,
  "wifiIP": "192.168.1.136",
  "apMode": false,
  "buildDate": "Feb 12 2026 03:18:44"
}
Field Type Description
startupLockout bool Whether the 5-minute startup lockout is active
startupLockoutRemainSec number Seconds remaining in startup lockout (0 when inactive)
shortCycleProtection bool Whether short-cycle protection delay is active on CNT
rvFail bool Whether RV fail (high suction temp during defrost) is latched
highSuctionTemp bool Whether suction temp is above threshold during defrost
defrostTransition bool Whether Phase 1 (pressure equalization) is active — entry or exit
defrostTransitionRemainSec number Seconds remaining in Phase 1 (0 when inactive)
defrostCntPending bool Whether Phase 2 (CNT hold) is active — entry or exit
defrostCntPendingRemainSec number Seconds remaining in Phase 2 (0 when inactive)
defrostExiting bool Whether a defrost exit transition is in progress (reverse 3-phase)
stateValidating bool Whether the state validation hold timer is active (blocking normal-priority transitions)
stateValidationRemainSec number Seconds remaining in state validation hold (0 when inactive)
manualOverride bool Whether manual override (pin control page) is active
manualOverrideRemainSec number Seconds remaining in manual override (0 when inactive)
cpuLoad0 number CPU load percentage for Core 0 (WiFi/protocol stack)
cpuLoad1 number CPU load percentage for Core 1 (Arduino loop/tasks)
freeHeap number Free heap memory in bytes
wifiSSID string Connected WiFi network name
wifiRSSI number WiFi signal strength in dBm
wifiIP string Device IP address
apMode bool Whether the device is in AP fallback mode
buildDate string Firmware build date and time (compile timestamp)
subcoolingF number Subcooling in °F (CONDENSER_TEMP - LIQUID_TEMP). Only present when both sensors are valid and compressor is running (HEAT/COOL/DEFROST)
safeMode bool Whether the device is in safe mode (crash recovery or forced)
crashBootCount number Number of consecutive crash boots (resets after 30s stable uptime)
resetReason string ESP32 reset reason (e.g., POWERON, SW_RESET, PANIC, INT_WDT)
rebootRateLimited bool Whether reboot API calls are rate-limited (clears after 5 min stable)

GET /temps/history

Returns temperature history CSV data for a specific sensor. Requires ?sensor= parameter.

List available files:

GET /temps/history?sensor=ambient
→ {"files":[{"date":"2026-02-11","size":56000},{"date":"2026-02-10","size":55800}]}

Download a day's CSV:

GET /temps/history?sensor=ambient&date=2026-02-11
→ 1739318400,48.1
  1739318430,48.2
  ...

Valid sensor names: ambient, compressor, suction, condenser, liquid

OTA Firmware Update Workflow

  1. POST /update — Upload firmware binary (saved to SD card as /firmware.new)
  2. GET /apply — Verify uploaded firmware exists and check size
  3. POST /apply — Backs up running firmware to /firmware.bak with build date metadata (/firmware.bak.meta), then flashes new firmware from SD and reboots
  4. POST /revert — Roll back to previous firmware from SD backup

If the new firmware causes a crash boot loop, the boot watchdog automatically reverts to the backup (see Crash Recovery).

MQTT Topics

The controller publishes to a configurable MQTT broker (default 192.168.0.46:1883) using QoS 1 (at-least-once delivery) for all publishes and subscribes. The topic prefix defaults to goodman but is configurable via system.mqttPrefix in config JSON or the config page, allowing multiple units on the same broker (e.g., unit1/temps, unit2/temps).

Subscribe with mosquitto_sub -t "goodman/#" to receive all topics (replace goodman with your configured prefix).

goodman/log

Log messages from the Logger. Published as plain text strings in the format:

[2026/02/10 14:32:01] [INFO] [HP] State changed: OFF -> HEAT

goodman/temps

Temperature sensor readings, published whenever any sensor value changes.

{
  "COMPRESSOR_TEMP": 72.5,
  "SUCTION_TEMP": 65.2,
  "AMBIENT_TEMP": 48.1,
  "CONDENSER_TEMP": 38.7,
  "LIQUID_TEMP": 185.3
}

Only sensors with valid readings are included. Values are in Fahrenheit.

goodman/state

Full controller state, published on every state transition, fault event, and compressor overtemp change.

{
  "state": "HEAT",
  "inputs": {
    "LPS": true,
    "DFT": false,
    "Y": true,
    "O": false
  },
  "outputs": {
    "FAN": true,
    "CNT": true,
    "W": false,
    "RV": false
  },
  "heatRuntimeMin": 42,
  "defrost": false,
  "defrostTransition": false,
  "defrostCntPending": false,
  "defrostExiting": false,
  "lpsFault": false,
  "lowTemp": false,
  "compressorOverTemp": false,
  "suctionLowTemp": false,
  "startupLockout": false,
  "startupLockoutRemainSec": 0,
  "shortCycleProtection": false,
  "rvFail": false,
  "highSuctionTemp": false,
  "stateValidating": false,
  "manualOverride": false,
  "coolTransition": false,
  "coolCntPending": false,
  "heatTransition": false,
  "heatCntPending": false,
  "defrostElapsedSec": 0
}
Field Type Description
state string Current state: OFF, HEAT, COOL, DEFROST, ERROR, or LOW_TEMP
inputs object Input pin active states (true = active)
outputs object Output pin states (true = on)
heatRuntimeMin number Accumulated HEAT mode CNT runtime in minutes
defrost bool Whether a software defrost cycle is active
defrostTransition bool Whether Phase 1 (pressure equalization) is active — entry or exit
defrostCntPending bool Whether Phase 2 (CNT hold) is active — entry or exit
defrostExiting bool Whether a defrost exit transition is in progress (distinguishes exit from entry)
lpsFault bool Whether an LPS low-pressure fault is active
lowTemp bool Whether LOW_TEMP protection is active (after 10-min validation)
lowTempPendingEntry bool Whether temp is below threshold and awaiting 10-min entry validation
lowTempPendingExit bool Whether temp is above threshold and awaiting 10-min exit validation
lowTempPendingRemainSec number Seconds remaining in LOW_TEMP entry/exit validation (0 when inactive)
compressorOverTemp bool Whether compressor temperature exceeds 240°F threshold
suctionLowTemp bool Whether suction temperature is critically low in COOL mode (< 32°F)
startupLockout bool Whether the 5-minute startup lockout is active
startupLockoutRemainSec number Seconds remaining in startup lockout (0 when inactive)
shortCycleProtection bool Whether short-cycle protection delay is active on CNT
rvFail bool Whether RV fail (high suction temp during defrost) is latched
highSuctionTemp bool Whether suction temp is above threshold during defrost
stateValidating bool Whether the state validation hold timer is active
manualOverride bool Whether manual override is active from pin control page
apMode bool Whether the device is in AP fallback mode

goodman/fault

Fault events, published when a fault activates or clears.

{
  "fault": "LPS",
  "message": "Low refrigerant pressure",
  "active": true
}

When the fault clears:

{
  "fault": "LPS",
  "message": "Low refrigerant pressure cleared",
  "active": false
}
Field Type Description
fault string Fault identifier (currently LPS)
message string Human-readable fault description
active bool true when fault activates, false when cleared

Build Notes

  • PSRAM allocation — Global operator new and operator delete are overridden in src/PSRAMAllocator.cpp to route all heap allocations through PSRAM via ps_malloc() when available, falling back to standard malloc() otherwise. PSRAM is initialized early using __attribute__((constructor(101))), which runs before C++ global constructors, ensuring PSRAM is available for any static object that allocates memory. The BOARD_HAS_PSRAM build flag must be defined in platformio.ini for the ESP-IDF framework to enable PSRAM support. This approach keeps allocation logic out of main.cpp and avoids per-allocation init checks.

  • AsyncTCP watchdog — The CONFIG_ASYNC_TCP_USE_WDT=0 build flag is required in platformio.ini. Without it, AsyncTCP subscribes its task to the ESP-IDF task watchdog (5s timeout). When the MQTT broker is slow or unreachable, the async_tcp task cannot reset the watchdog in time, causing a panic and reboot. This flag prevents the async_tcp task from registering with the watchdog.

  • HTTPS server separationHttpsServer.cpp is in a separate translation unit because esp_https_server.h (ESP-IDF) and ESPAsyncWebServer.h both define HTTP_PUT, HTTP_OPTIONS, and HTTP_PATCH enums and cannot coexist in the same TU. Logger.h forward-declares AsyncWebSocket to avoid pulling in the ESPAsyncWebServer header chain.

Known Issues

MCP9600 I2C Bus Crash

Some MCP9600 thermocouple amplifier chips have a hardware bug where a bare I2C address probe (sending only the address byte with no register data via beginTransmission/endTransmission) crashes the chip and locks up the entire I2C bus. The chip remains unresponsive until power cycled — a software reboot is not sufficient to recover it.

Workaround implemented: The firmware initializes the MCP9600 via its Adafruit driver (which performs a full Device ID register read at 0x20) before any I2C bus scan, and skips address 0x67 in all scan loops. The /i2c/scan web endpoint uses a full register read instead of a bare probe for 0x67. The Adafruit MCP9600 library itself already passes begin(false) internally to skip the bare probe — the issue was only with the generic I2C scan code.

If the MCP9600 stops responding after flashing firmware that performed bare I2C scans, a full power cycle (unplug power, not just software reboot) will recover it.

Reference: Adafruit Forums — MCP9600 I2C issues

Known Bugs

All bug reports in docs/bugs/.

# Description Severity Fixed In
BUG-001 Defrost exit turns on CNT+FAN with Y inactive — compressor runs without indoor airflow. _defrostStartTick=0 causes false 15-min timeout when Y drops during Phase 1/2, triggering exit sequence that turns on compressor without checking Y. Suction temp peaked at 148°F. Critical 028e568
BUG-002 Manual override bypasses startup lockout — CNT can be turned ON 69 seconds after reboot during 180s lockout period. setManualOverride() and setManualOutput() did not check _startupLockout. Short cycle condition had redundant AND making it ineffective after 30s. High 6f0871c
BUG-003 Config-loaded sensors marked valid=true on boot with stale cached last-value: 0. checkAmbientTemp() sees 0.0°F < threshold and triggers false LOW_TEMP protection on every reboot — shutting down CNT, turning on W for ~10s until real OneWire data arrives. 77 false triggers across 263 reboots in first 18-day deployment. High d49d2e8
BUG-004 W relay turned ON during defrost Phase 1 — race condition in updateState() where W control block ran before Phase 1 restart set _defrostTransition=true. Validator auto-corrected. 6 occurrences (Feb 25–Mar 1). Medium 46d3a0f
BUG-005 FAN not restored after manual override exit — _yWasActive not reset so Y activation edge never re-fired. Validator auto-corrected. 1 occurrence (Feb 25). Low f7f3cf4
BUG-006 FAN validator fight during state validation window — validator enforced OFF rules against stale state label while FAN was correct for pending HEAT transition. Double-correction. 2 occurrences (Feb 28). Low f7f3cf4
BUG-007 RV relay turned off under pressure without equalization delay — 9 code paths called rv->turnOff() directly while system still under compressor discharge pressure. Fix: safeRvOff() helper defers RV off until _rvShortCycleMs after CNT off. Medium 2b8a199
BUG-008 OTA upload hangs device — HTTPS httpd task does httpd_req_recv() + SD.write() in tight loop, concurrent SD access from main loop tasks corrupts SPI bus → deadlock. Fix: buffer firmware in PSRAM, single SD write. High a75ab7b
BUG-009 Defrost triggers in OFF state — checkDefrostNeeded() had no state guard before runtime threshold check, allowing defrost to start while Y inactive. Y-abort safety gate caught it within 500ms. Fix: gate new-defrost trigger on State::HEAT. 1 occurrence (Mar 3). Low 932b969
BUG-010 Defrost band display stuck on Warm in OFF/COOL — BUG-009 regression. selectDefrostBand() was below the HEAT guard so _activeDefrostBand never updated outside HEAT mode. Fix: moved band selection above guard. Low fd030e4

Dependencies

Managed automatically by PlatformIO. Key libraries: