Raspberry Pi 5 Advanced Fan Controller

简体中文 | English

Predictive Zone MPC fan control: about 28.5% lower theoretical fan-side power at the same mean temperature

A Raspberry Pi 5 advanced fan controller using Zone MPC.

Instead of waiting for the SoC to cross a few fixed temperature thresholds, this project predicts the near-future thermal trajectory and chooses a PWM that keeps the machine inside a target temperature zone.

The user-visible result is a fan strategy that plans ahead and spends fan effort more deliberately. On the 10-minute AB test on this Pi (see Measured Result):

  • At a matched average temperature (~57.9 C), Zone MPC ran at lower average and much lower median fan RPM than the scaled official ladder (median 3647 vs 5816 RPM) — quieter on average for the same cooling.
  • Controller CPU and memory cost on the Pi 5 is negligible (~0.65 s of CPU over 600 s).
  • Within the target zone it prefers the lowest PWM that still protects the zone, and idles the fan when the predicted trajectory stays cool.
  • It does not eliminate transient overshoot: peak temperature under sudden load bursts was similar to the baseline (62.2 vs 61.7 C), because workload spikes are exogenous and cannot be predicted from thermal history.

Implementation standard:

M2 second-order ARX predictor + Zone MPC

Why This Exists

The stock kernel fan policy is simple and robust, but it is reactive: it maps temperature thresholds to fixed PWM steps. That is easy to reason about, but it cannot ask a richer question:

Given current temperature, fan PWM, CPU load, and recent history,
what PWM keeps the next few control steps inside the desired zone
with the least fan effort?

This controller answers that question every control interval.

Measured Result

The current public story is based on a real 10 minute AB run on a Raspberry Pi 5:

  • Same randomized CPU-load seed for both arms.
  • Start temperature delta: 0.55 C.
  • Target zone: 53-58 C.
  • Baseline: official temperature ladder, with PWM scaled to 75% so its average temperature is close to Zone MPC.
  • Raw CSV/JSON logs are excluded from the repository; the README uses curated figures only.

AB curves comparing scaled official fan steps with Zone MPC

Summary of fan effort and theoretical fan-side power saving

Metric Scaled official step Zone MPC
Mean temperature 57.88 C 57.99 C
Peak temperature 61.70 C 62.25 C
Seconds above 58 C 287.71 s 268.76 s
Average PWM 158.64 152.13
Average RPM 5533.54 4948.01
Median RPM 5816 3647
Controller CPU time over 600 s 0.2351 s 0.6536 s

Using the common fan affinity approximation fan power ~= RPM^3, the AB run estimates:

  • Against the temperature-matched scaled official ladder: average fan-side power index dropped from 100% to about 71.5%, or roughly 28.5% theoretical fan-side saving.
  • Against the original unscaled official ladder from the comparison run: average RPM was 4715 vs 7219, giving a theoretical fan-side saving of about 72%. That comparison is intentionally labeled less fair because the original ladder also ran cooler and louder.

This is not a whole-system wattmeter measurement. It is a fan-side theoretical estimate from measured RPM, useful for comparing control policies with similar thermal targets.

Quick Install

Clone the project to the expected runtime path:

cd /home/pi
git clone https://github.com/Zhenyu98/pi-fan-control.git fan-control
cd /home/pi/fan-control

Run a no-write dry check first:

python3 /home/pi/fan-control/src/fan_control.py --dry-run --duration 20

Install and start the service:

sudo cp /home/pi/fan-control/fan-control.service /etc/systemd/system/fan-control.service
sudo cp /home/pi/fan-control/fan-control-dashboard.service /etc/systemd/system/fan-control-dashboard.service
sudo cp /home/pi/fan-control/fan-control-maintenance.service /etc/systemd/system/fan-control-maintenance.service
sudo cp /home/pi/fan-control/fan-control-maintenance.timer /etc/systemd/system/fan-control-maintenance.timer
sudo systemctl daemon-reload
sudo systemctl enable --now fan-control.service
sudo systemctl enable --now fan-control-dashboard.service
sudo systemctl enable --now fan-control-maintenance.timer

Check it:

systemctl status fan-control.service
systemctl status fan-control-dashboard.service
journalctl -u fan-control.service -n 50 --no-pager

Open the read-only dashboard from another device on the LAN:

http://<raspberry-pi-ip>:8766/

Current Product Decision

This project is standardized on Zone MPC with a second-order ARX thermal predictor.

The previous single-setpoint controller has been removed from the runtime path. Historical reports may mention earlier experiments, but the supported controller is now the predictive zone controller.

Default policy:

  • Target zone: 53-58 C
  • Stable first fan step: min_active_pwm=75
  • PWM ramp limit: max_step=20
  • Full speed threshold: 69 C
  • Safety threshold: 70 C
  • Model: /home/pi/fan-control/data/model_arx2_m2.json

How It Works

M2 ARX Predictor

The active model is a second-order ARX thermal predictor:

T_next =
  a0 * T_now
+ a1 * T_previous
+ b0 * PWM_now
+ b1 * PWM_previous
+ c0 * load_now
+ c1 * load_previous
+ bias

Using previous temperature, previous PWM, and previous load makes the model better at short rollout prediction than a simple first-order model. This matters because MPC decisions are based on a horizon, not just one immediate step.

How well does it actually predict? On a held-out randomized-stress run the model was not fit on, the one-step prediction tracks the measured SoC temperature with a mean absolute error of about 0.66 C. Because MPC plans over a horizon, the right-hand panel also shows how rollout error grows with the prediction length, from about 0.7 C at one step to about 1.9 C at twelve steps (~24 s ahead).

ARX2 predictor accuracy: one-step prediction tracks measured temperature within ~0.66 C on a held-out run, with rollout error growing gradually with horizon

Is 0.66 C large? It is close to the floor set by the hardware, not a sign of a weak model. The Pi's thermal sensor only resolves about 0.55 C — every logged reading sits on a 0.55 °C grid — so rounding to the nearest sensor tick alone costs about 0.27 C on average. For comparison, a naive "next = current" persistence predictor scores the same 0.64 C MAE on this run, and the model's error is concentrated almost entirely on the few steps where CPU load suddenly changes (1.56 C on load-change steps vs 0.62 C on steady steps). In other words, the one-step error is dominated by sensor quantization and unpredictable load steps rather than model bias. The model earns its value over the rollout horizon and by reasoning about the effect of changing PWM, which a persistence guess cannot do.

Zone MPC Controller

Zone MPC evaluates candidate PWM values and rolls the model forward over the prediction horizon.

It prefers:

  • temperatures inside the 53-58 C zone,
  • low PWM,
  • small PWM changes,
  • no sustained predicted violation above 58 C,
  • no predicted approach to the 69 C full-speed threshold.

It also includes a conservative prediction observer. If the model has recently underpredicted temperature, the controller adds a bounded prediction margin, so future MPC scoring becomes more cautious.

Core Contribution

This project contributes a practical predictive fan-control path for Raspberry Pi 5 users:

  • A controller that plans ahead instead of only reacting after a threshold is crossed.
  • A zone target that makes the behavior easier to tune than a single fixed setpoint.
  • Conservative prediction margins and high-temperature penalties to avoid systematic undercooling.
  • Shadow learning that can improve the model without letting unvalidated models directly control the fan.
  • A public, repeatable AB test script for comparing Zone MPC, constant MPC, and official-step policies.
  • Evidence that, at a similar thermal target, Zone MPC can reduce fan-side theoretical power by about 28.5% in the current AB run while keeping controller CPU overhead effectively negligible.
  • A fast, low-cost educational project: an end-to-end ARX system identification + Zone MPC loop running on real $10-class hardware, with held-out prediction metrics and reproducible AB scripts — a compact, hands-on case study for anyone who already understands MPC and wants to see it applied on a physical plant.

Files

The repository is split into the runtime that the service needs and the offline tooling used to build models and benchmark policies.

src/ — runtime (what fan-control.service actually runs):

  • fan_control.py: live ARX2 Zone MPC controller.
  • fan_control_core.py: thermal models, ARX2 fitting, prediction observer, Zone MPC.
  • fan_control_shadow.py: shadow learning and safe model promotion.
  • fan_control_io.py: sysfs discovery and fan I/O.
  • dashboard_server.py: read-only HTTP dashboard API and static file server.
  • dashboard.html: live dashboard for temperature, PWM, RPM, and load.
  • fan_safe.py: systemd stop-post fallback.
  • fan_control_maintenance.py: journal and experiment-artifact cleanup.

tools/ — offline research and dev tooling (not required to run the service):

  • collect.py: data collection.
  • fit_model.py: ARX2 model fitting from collected samples.
  • identify_model.py: dedicated load/PWM identification experiment.
  • model_identification.py: identification schedule and model-comparison library.
  • compare_models.py: model comparison report generator.
  • evaluate.py: pressure test and controller overhead measurement.
  • random_stress_test.py: randomized pressure phases with prediction metrics.
  • ab_mpc_test.py: side-by-side AB test that drives Zone MPC, constant MPC, and the scaled official ladder under the same load seed, and renders the comparison figures.

Each tools/ script imports _pathfix first so the src/ runtime modules resolve when it is launched directly.

Project root — service units and tests:

  • fan-control.service: systemd service template.
  • fan-control-dashboard.service: read-only dashboard service on port 8766.
  • fan-control-maintenance.service: cleanup service for journal and experiment artifacts.
  • fan-control-maintenance.timer: daily cleanup timer.
  • tests/: unit tests (python3 -m pytest); conftest.py puts src/ and tools/ on the import path.

The scripts auto-discover the current /sys/class/hwmon/hwmon*/name == pwmfan device at startup, so they do not depend on the hwmonN number staying fixed across reboots.

Quick Check

Run without touching PWM:

python3 /home/pi/fan-control/src/fan_control.py --dry-run --duration 20

Expected log fields include:

mode=zone-mpc
prediction_margin=...
predicted_max=...
terminal=...
violation_steps=...
reason=...

Run Manually

Run the controller for two minutes:

sudo python3 /home/pi/fan-control/src/fan_control.py --duration 120

The controller restores automatic fan mode on exit.

On this Pi, pwm1_enable=1 is the effective writable mode. A quick probe showed PWM 40 does not spin the fan, PWM 60 barely spins it, and PWM 75 is the stable first step. The controller therefore avoids tiny non-spinning PWM outputs.

Shadow Learning

The service runs with --shadow-learn.

Shadow learning does not directly control the fan. The active controller keeps using the current stable ARX2 model while the learner records live samples to:

/home/pi/fan-control/data/shadow_samples.csv

Every check interval, it fits a candidate model from the rolling sample window. For the current runtime, the candidate is also ARX2. Promotion requires:

  • enough samples,
  • enough temperature, PWM, and load variation,
  • aggregate PWM coefficient remains cooling,
  • aggregate load coefficient remains heating,
  • ARX temperature memory stays inside conservative bounds,
  • high-temperature bias is not systemically underpredicting,
  • prediction MAE improves by the configured minimum.

If accepted, the learner atomically writes the current model path and hot-loads the new controller. It keeps only:

current model
previous model

The sample log rotates to one .1 file, so long-running learning data does not grow without bound.

Logging And Retention

The live controller no longer writes routine journal logs every control interval. By default, fan_control.py logs one routine status line every 30 seconds:

python3 /home/pi/fan-control/src/fan_control.py --log-interval 30

Important events still log immediately:

  • PWM changes,
  • sustained predicted zone violations,
  • full-speed or safety decisions,
  • shadow-learning decisions and promotions.

The systemd unit also sets journald rate-limit fields as a backstop:

LogRateLimitIntervalSec=60
LogRateLimitBurst=120

Cleanup is handled by fan_control_maintenance.py. The default policy keeps recent artifacts and removes older experiment output:

python3 /home/pi/fan-control/src/fan_control_maintenance.py --dry-run
sudo python3 /home/pi/fan-control/src/fan_control_maintenance.py

Default retention:

  • acceptance artifacts: remove old run directories after 14 days, while keeping the latest 5,
  • evaluation artifacts: remove old data/evaluation-*.json files after 14 days, while keeping the latest 5,
  • journal: run journalctl --vacuum-time=14d --vacuum-size=200M.

Note: journal vacuum is global to systemd-journald, not per service. The controller reduces its own log volume with --log-interval; the vacuum command keeps the journal store bounded.

Collect And Fit

For a quick local fit from collected samples:

python3 /home/pi/fan-control/tools/collect.py --duration 600 --interval 2
python3 /home/pi/fan-control/tools/fit_model.py

For a better model, use the dedicated identification experiment:

sudo python3 /home/pi/fan-control/tools/identify_model.py
python3 /home/pi/fan-control/tools/compare_models.py --input /home/pi/fan-control/data/identification/<run>/samples.csv

The model selection rule is intentionally conservative:

  • do not promote a model only because one-step error is low,
  • check rollout error because MPC depends on prediction horizon,
  • require cooling sign for PWM,
  • require heating sign for load,
  • reject high-temperature systematic underprediction.

Evaluate

Run a short pressure test and overhead measurement:

sudo python3 /home/pi/fan-control/tools/evaluate.py --duration 90 --workers 4

Run randomized pressure phases:

python3 /home/pi/fan-control/tools/random_stress_test.py --duration 660 --interval 2 --min-phase 20 --max-phase 75 --max-workers 4 --model /home/pi/fan-control/data/model_arx2_m2.json

For a no-write check:

python3 /home/pi/fan-control/tools/evaluate.py --duration 30 --workers 2 --dry-run

Service

Install:

sudo cp /home/pi/fan-control/fan-control.service /etc/systemd/system/fan-control.service
sudo cp /home/pi/fan-control/fan-control-dashboard.service /etc/systemd/system/fan-control-dashboard.service
sudo cp /home/pi/fan-control/fan-control-maintenance.service /etc/systemd/system/fan-control-maintenance.service
sudo cp /home/pi/fan-control/fan-control-maintenance.timer /etc/systemd/system/fan-control-maintenance.timer
sudo systemctl daemon-reload
sudo systemctl enable --now fan-control.service
sudo systemctl enable --now fan-control-dashboard.service
sudo systemctl enable --now fan-control-maintenance.timer

Check:

systemctl status fan-control.service
systemctl status fan-control-dashboard.service
journalctl -u fan-control.service -n 50 --no-pager
systemctl list-timers fan-control-maintenance.timer

Disable the user-space service and set a safe fallback PWM:

sudo systemctl disable --now fan-control.service
sudo systemctl disable --now fan-control-dashboard.service
sudo systemctl disable --now fan-control-maintenance.timer
sudo python3 /home/pi/fan-control/src/fan_safe.py

Dashboard

The optional dashboard is a read-only HTTP view of local controller data:

sudo systemctl enable --now fan-control-dashboard.service
curl http://127.0.0.1:8766/api/status

Open it from the LAN:

http://<raspberry-pi-ip>:8766/

Endpoints:

  • /: live dashboard HTML.
  • /api/status: latest sample, service state, configured target zone.
  • /api/latest?minutes=60&max_points=1800: recent samples for plotting.
  • /api/summary?hours=4: aggregate temperature, PWM, RPM, load, and zone metrics.

The dashboard reads data/shadow_samples.csv, supports HEAD health checks, and never writes PWM.

Kernel Fan Policy

The current /boot/firmware/config.txt does not contain active custom dtparam=fan_temp* or dtparam=cooling_fan lines.

While fan-control.service is running, the user-space controller owns PWM. If the service stops, ExecStopPost runs fan_safe.py, which sets a safe PWM based on current temperature.

If custom fan_temp* entries are added later, treat them as a fallback policy rather than the primary controller.

Safety And Privacy

  • The controller auto-discovers the Raspberry Pi fan hwmon device instead of depending on a fixed hwmonN path.
  • fan_safe.py is used as a systemd stop-post fallback so service shutdown does not leave the fan in a risky state.
  • safety_temp forces full-speed cooling before the SoC reaches a dangerous range.
  • Shadow learning records local thermal samples only and does not upload data.
  • Raw logs, samples, and experiment outputs are ignored by git and are not part of the public release.

FAQ

Will it be quieter than the default kernel fan policy?

Not guaranteed. In the AB test on this Pi, at a matched average temperature Zone MPC used lower average and much lower median RPM than the scaled official ladder, so on that run it was quieter on average for the same cooling. But the stock policy can always be colder by simply running the fan harder, and during sudden load bursts Zone MPC's fan speed can still rise sharply. The goal is to spend fan effort where the predicted trajectory needs it, not to be unconditionally quiet.

Does online learning directly control the fan?

No. Shadow learning can propose a better model only after safety checks. The active controller keeps using the current validated model until a candidate passes conservative promotion rules.

Can I keep dtparam=fan_temp* in config.txt?

Treat those entries as fallback policy. While fan-control.service is running, user-space owns PWM. If the service stops, the fallback and fan_safe.py protect the machine.

Does this need network access?

No runtime network access is required.

Roadmap

  • Anticipatory pre-cooling before known heavy workloads, to bank thermal margin. Today the controller is reactive-predictive: it only spins up after load and temperature start rising, and its MPC rollout assumes future load equals the current load, so it cannot pre-cool for a task that has not started yet. The thermal model already takes load as a rollout input, so the architecture is ready — what is missing is a short future-load forecast. Feeding one in (an explicit "job starting" signal from the workload, cron/systemd-timer awareness of scheduled jobs, or a learned workload predictor built on the existing shadow samples) would let MPC raise PWM early and enter a heavy task with extra stability margin instead of reacting after the temperature climbs.
  • Broaden identification data across more ambient temperatures and cases.
  • Add optional RPM-aware model validation for boards where RPM readings are reliable.
  • Provide a packaged installer that can migrate from the current manual systemd copy flow.
  • Add a concise dashboard or text UI for live temperature, PWM, RPM, and prediction margin.