loxalarm

CI Release

Deterministic alarm-state core for embedded C firmware.

loxalarm is a small, heap-free C99 library that implements the runtime state model of a process alarm: on-delay, off-delay, latch, acknowledge, shelving, and reason flags.

It is designed for MCU firmware that needs PLC-style alarm semantics (latch-until-acked, shelve-without-losing-events, chattering suppression) without depending on a PLC vendor stack, an HMI, an OS, or dynamic memory.

#include "loxalarm/loxalarm.h"

static lox_alarm_t pressure_alarm;

static const lox_alarm_config_t pressure_alarm_cfg = {
    .on_delay_ms       = 2000,   // condition must hold 2 s before active
    .off_delay_ms      = 5000,   // must clear 5 s before inactive
    .latched           = true,   // requires explicit ack
    .shelvable         = true,
    .max_shelve_ms     = 15 * 60 * 1000, // 15 min cap
};

lox_alarm_init(&pressure_alarm, &pressure_alarm_cfg);

// in your control loop:
lox_alarm_update(&pressure_alarm, pressure_above_limit, now_ms);

if (lox_alarm_is_active(&pressure_alarm)) {
    raise_horn();
}

What loxalarm is

A single, well-defined runtime object: one alarm condition with one lifecycle. You instantiate as many as you need; each owns its own state struct (caller-allocated).

The lifecycle is modelled on the alarm states used by ISA 18.2 and OPC UA Part 9 (Alarms & Conditions):

                  +-------------+
                  |  NORMAL     |
                  +------+------+
                         |
              condition true >= on_delay
                         v
                  +-------------+
            +----->  ACTIVE     +-----+
            |     +------+------+     |
            |            |            |
            |   condition false       |  shelve()
            |   >= off_delay          v
            |            |     +------+------+
            |            |     |  SHELVED    |
            |            |     +------+------+
            |            |            |
            |            v   max_shelve_ms timeout
            |     +-------------+     |
            +-----+ LATCHED-RTN <-----+
                  +------+------+
                         |
                       ack()
                         v
                  +-------------+
                  |  NORMAL     |
                  +-------------+

(See docs/state-model.md for the full state table including out-of-service.)

What loxalarm is not

  • It is not a safety-rated alarm system. It does not claim SIL compliance, IEC 61508 conformance, or any functional safety certification.
  • It is not an HMI or alarm history database. It exposes transitions; you decide how to render or persist them.
  • It is not a network protocol. There is no built-in OPC UA, MQTT, or Modbus binding. Those live in adapter layers above loxalarm.
  • It is not a generic FSM. Use microfsm for arbitrary state machines. loxalarm implements one specific, well-known state model: the alarm.

Design rules

  • C99, no compiler extensions.
  • Single-header distribution option (loxalarm/loxalarm_single.h).
  • No heap - all state is caller-owned (lox_alarm_t on stack or in static memory).
  • No floating point. Time is uint32_t milliseconds, supplied by the caller.
  • No global mutable state. Every function takes the alarm pointer.
  • No HW dependency. Caller passes the current condition (bool) and the current monotonic time. Time source is your business.
  • Deterministic. lox_alarm_update() has O(1) work and a bounded set of state transitions per call.
  • Reentrancy: per-instance. Two alarms can be updated from two threads without locks. The same alarm from two contexts is not supported.

Minimum viable use

#include "loxalarm/loxalarm.h"

lox_alarm_t a;
lox_alarm_init(&a, &(lox_alarm_config_t){ .latched = true });

while (running) {
    bool cond = read_sensor() > 80;
    lox_alarm_update(&a, cond, get_monotonic_ms());

    if (lox_alarm_just_activated(&a)) {
        log_event("HIGH_TEMP raised");
    }
    if (lox_alarm_just_returned(&a)) {
        log_event("HIGH_TEMP returned to normal");
    }
}

// operator acknowledged via shell or HMI:
lox_alarm_ack(&a, get_monotonic_ms(), OPERATOR_ID);

What problem this solves

Process firmware repeatedly hand-rolls alarm logic:

// the bad version that lives in 10 000 firmware projects
if (pressure > LIMIT) {
    if (!alarm_state) {
        alarm_state = true;
        alarm_time  = now;
        log("ALARM");
    }
} else if (alarm_state && (now - alarm_time > 3000)) {
    alarm_state = false;
}

That snippet has at least five real problems:

  • no on-delay (chattering at threshold causes alarm flap)
  • no clear separation between signal logic and alarm semantics
  • no latch (alarm vanishes before operator sees it)
  • no acknowledge (no concept of operator-aware reset)
  • no shelve (cannot temporarily silence during maintenance without losing the underlying state)

loxalarm provides one tested, predictable implementation of all of these.

Note: loxalarm consumes a boolean condition; if you need hysteresis, implement it in your signal/threshold logic before calling lox_alarm_update() (see docs/state-model.md).

Comparison

Aspect Rockwell P_Alarm OPC UA UA Server loxalarm
Target platform PLC (Logix) Server-side MCU C99
Heap allocation n/a yes no
Vendor lock-in Rockwell OPC Foundation none
State model Ack/Shelf/Supp ISA 18.2 full ISA 18.2 subset
HMI binding included yes yes no
Audit / history included yes yes no
Suitable for bare-metal MCU no no yes

loxalarm is intentionally narrower than either. It is the runtime alarm object - not the HMI, not the historian, not the server.

Integration with the Lox family

  • microhealth - provides the input condition (is_overheat()).
  • microconf - stores limits, delays, shelve duration as config.
  • microlog - receives transition events for the audit trail.
  • microsh - exposes alarm ack, alarm shelve, alarm list commands.
  • nvlog / loxdb - optional persistence of the latched and shelved states across reboot. (loxalarm does not persist by itself; it offers a snapshot/restore pair if persistence is wanted.)

Building

Drop the include/ directory into your project. There is nothing to link.

#include "loxalarm/loxalarm.h"

// or, for projects that prefer one-header builds:
#include "loxalarm/loxalarm_single.h"

The implementation is header-only (static inline) in v0.1.

CMake

cmake -S . -B build
cmake --build build

Status

Pre-1.0. Public API is not stable yet. Semver applies from v1.0.0 onwards.

License

MIT. See LICENSE.