+.. note::
+
+ AMD Instinct systems vary in form and configuration, and cluster design adds additional layers of complexity. The
+ guidelines in this documentation are written at a high level for broad applicability across diverse environments.
+ While certain scenarios may include specific hardware examples, your setup will likely differ in terms of GPUs and
+ CPUs per server, firmware versions, and network interconnects. Adjustments might be necessary to align with your
+ particular configuration.
diff --git a/docs/sphinx/_toc.yml b/docs/sphinx/_toc.yml
index 052ef65..e4ae606 100644
--- a/docs/sphinx/_toc.yml
+++ b/docs/sphinx/_toc.yml
@@ -3,6 +3,9 @@ defaults:
maxdepth: 6
root: index
subtrees:
+- entries:
+ - file: overview.rst
+ title: Overview
- caption: How to
entries:
- file: how-to/gpu-enabled-mpi
diff --git a/docs/sphinx/_toc.yml.in b/docs/sphinx/_toc.yml.in
index 052ef65..e4ae606 100644
--- a/docs/sphinx/_toc.yml.in
+++ b/docs/sphinx/_toc.yml.in
@@ -3,6 +3,9 @@ defaults:
maxdepth: 6
root: index
subtrees:
+- entries:
+ - file: overview.rst
+ title: Overview
- caption: How to
entries:
- file: how-to/gpu-enabled-mpi
diff --git a/infrastructure/dc-design/.readthedocs.yaml b/infrastructure/dc-design/.readthedocs.yaml
new file mode 100644
index 0000000..dfc04da
--- /dev/null
+++ b/infrastructure/dc-design/.readthedocs.yaml
@@ -0,0 +1,31 @@
+# Read the Docs configuration file
+# See https://docs.readthedocs.io/en/stable/config-file/v2.html for details
+
+version: 2
+
+build:
+ os: ubuntu-22.04
+ tools:
+ python: "3.10"
+ jobs:
+ post_checkout:
+ # Monorepo guard: cancel the build unless this change touched infrastructure/dc-design/
+ # Fetch develop's history (not just its tip) so the common ancestor with
+ # this branch is reachable, then review every commit since that ancestor.
+ - git fetch origin develop || true
+ - |
+ BASE=$(git merge-base origin/develop HEAD || true)
+ # Fail open: if no common ancestor is found (e.g. develop history not
+ # fetched on a PR build), build rather than risk cancelling wrongly.
+ if [ -n "$BASE" ] && git diff --quiet "$BASE" HEAD -- infrastructure/dc-design/; then
+ exit 183
+ fi
+python:
+ install:
+ # Shared across all docsets; dependabot tracks this single file (.github/dependabot.yml)
+ - requirements: docs/sphinx/requirements.txt
+
+sphinx:
+ configuration: infrastructure/dc-design/conf.py
+
+formats: [htmlzip]
diff --git a/infrastructure/dc-design/_static/css/custom.css b/infrastructure/dc-design/_static/css/custom.css
new file mode 100644
index 0000000..25e0f44
--- /dev/null
+++ b/infrastructure/dc-design/_static/css/custom.css
@@ -0,0 +1,41 @@
+/* Disable the instinct-design theme's scroll-reveal animation: its JS sets
+ sections to opacity:0 until scrolled into view, which makes long pages
+ appear to "load in" on scroll. Force all sections fully visible so the
+ whole page renders at once (matching the old "instinct" flavor). */
+.bd-main section[id] {
+ opacity: 1 !important;
+ transform: none !important;
+}
+
+/* Hide the primary sidebar toggle (carat) only when the primary sidebar is
+ empty. */
+.bd-container__inner:has(.bd-sidebar-primary.hide-on-wide) .sidebar-toggle.primary-toggle {
+ display: none;
+}
+
+/* Remove white background from topology diagrams in dark mode */
+html[data-theme=dark] .bd-content img {
+ background-color: transparent !important;
+}
+
+/* Restore normal brightness for images in dark mode */
+html[data-theme=dark] .bd-content img:not(.only-dark,.dark-light) {
+ filter: brightness(1) contrast(1) !important;
+}
+
+/* Add neutral grey background for images in light mode */
+html:not([data-theme=dark]) .bd-content img {
+ background-color: #777 !important;
+}
+
+/* Shrink the Legal information section heading */
+ #legal-information > h2 {
+ font-size: 1rem;
+ }
+
+ /* Render the Legal information body text smaller (see .. container:: legal-text
+ in index.rst) */
+.legal-text {
+ font-size: 0.65rem;
+ line-height: 1.4;
+}
\ No newline at end of file
diff --git a/infrastructure/dc-design/conf.py b/infrastructure/dc-design/conf.py
new file mode 100644
index 0000000..5fd146a
--- /dev/null
+++ b/infrastructure/dc-design/conf.py
@@ -0,0 +1,264 @@
+"""Configuration file for the Sphinx documentation builder."""
+import os
+import re
+from pathlib import Path
+
+html_baseurl = os.environ.get("READTHEDOCS_CANONICAL_URL", "instinct.docs.amd.com")
+html_context = {}
+if os.environ.get("READTHEDOCS", "") == "True":
+ html_context["READTHEDOCS"] = True
+
+html_title = "Data Center Design Guide"
+author = "Advanced Micro Devices, Inc."
+copyright = "Copyright (c) 2026 Advanced Micro Devices, Inc. All rights reserved."
+version = "1.0"
+release = version
+setting_all_article_info = False
+
+external_toc_path = "./sphinx/_toc.yml"
+
+external_projects_current_project = "dc-design"
+external_projects_remote_repository = ""
+
+html_theme = "rocm_docs_theme"
+html_theme_options = {
+ "flavor": "instinct-design",
+ "show_toc_level": 2,
+ "navbar_align": "content",
+ "link_main_doc": True,
+ "use_download_button": True,
+}
+extensions = ["rocm_docs"]
+
+html_static_path = ['_static']
+
+# Disable sidebars to handle minimal TOC
+html_sidebars = {
+ "**": []
+}
+
+
+html_extra_path = ["llms.txt"]
+
+EXCLUDED_DIRS = {
+ "_build",
+ "_templates",
+ "_static",
+ ".git",
+ ".venv",
+}
+
+MARKUP_PREFIXES = (
+ ":::",
+ "```{",
+ "```",
+ ":img-top:",
+ ":class",
+ ":link:",
+ ":link-type:",
+ ":shadow:",
+ ":columns:",
+ ":padding:",
+ ":gutter:",
+ ":open:",
+ ":name:",
+ ":header-rows:",
+ ":alt:",
+ "+++",
+ "-->",
+ "{bdg-",
+)
+
+# Matches lines like "align: center", "alt:", "name: foo" (directive options
+# not starting with a colon, common in MyST figure/table fences)
+_BARE_DIRECTIVE_RE = re.compile(r"^[a-z][a-z_-]*:\s*\S*$")
+
+# Matches MyST/RST anchor labels like "(some-label)="
+_ANCHOR_LABEL_RE = re.compile(r"^\(\w[\w-]*\)=$")
+
+# Matches RST section underlines (e.g. "====", "----", "~~~~")
+_RST_UNDERLINE_RE = re.compile(r"^[=\-~^\"\'#*+]{3,}$")
+
+# Matches RST code block directives (e.g. ".. code-block:: cpp", ".. code:: sh")
+_RST_CODE_BLOCK_RE = re.compile(r"^\.\.\s+(code-block|code|sourcecode)::")
+
+# Matches markdown table separator rows (e.g. "|---|---|", "| :--- | ---: |").
+_MD_TABLE_SEP_RE = re.compile(r"^\|[\s|:\-]+\|$")
+
+# Matches RST directives whose indented body should be discarded (e.g. raw HTML).
+_RST_SKIP_BLOCK_RE = re.compile(r"^\.\.\s+raw::")
+
+# Matches HTML tags (e.g. "", "", " block
+ in_html_open_tag = False # inside a multi-line HTML opening tag
+ kept = []
+ for line in lines:
+ stripped = line.strip()
+ # Backtick fences (MyST/Markdown)
+ if stripped.startswith("```"):
+ in_backtick_fence = not in_backtick_fence
+ kept.append(line)
+ continue
+ if in_backtick_fence:
+ kept.append(line)
+ continue
+ # HTML comment block (): discard all content until -->
+ if in_html_comment:
+ if "-->" in stripped:
+ in_html_comment = False
+ continue
+ # RST skip block (e.g. .. raw::): discard all indented content
+ if in_rst_skip_block:
+ if not stripped or line[0] in (" ", "\t"):
+ continue
+ in_rst_skip_block = False
+ # RST code block: exit when a non-blank, non-indented line appears
+ if in_rst_code_block:
+ if not stripped or line[0] in (" ", "\t"):
+ kept.append(line)
+ continue
+ in_rst_code_block = False
+ # RST raw block: enter and discard both the directive and its body
+ if _RST_SKIP_BLOCK_RE.match(stripped):
+ in_rst_skip_block = True
+ continue
+ # RST code block: enter on directive line (directive itself is dropped)
+ if _RST_CODE_BLOCK_RE.match(stripped):
+ in_rst_code_block = True
+ continue
+ # HTML comment open (): discard opener and enter state
+ if stripped.startswith("" not in stripped:
+ in_html_comment = True
+ continue
+ # Multi-line HTML opening tag: skip continuation lines until >
+ if in_html_open_tag:
+ if ">" in stripped:
+ in_html_open_tag = False
+ continue
+ # Detect HTML opening tags that wrap across lines (no > on this line)
+ if _HTML_TAG_RE.match(stripped) and ">" not in stripped:
+ in_html_open_tag = True
+ continue
+ if not stripped:
+ kept.append(line)
+ elif is_prose_line(line):
+ # Strip trailing HTML close tags (e.g. "See the guide.")
+ cleaned = _TRAILING_HTML_CLOSE_RE.sub("", line).rstrip()
+ cleaned_stripped = cleaned.strip()
+ if not cleaned_stripped:
+ # Entire line was HTML close tags — keep original (shouldn't
+ # normally reach here since _is_prose_line filters HTML).
+ kept.append(line)
+ elif re.search(r"\w", cleaned_stripped):
+ # Line has real word content after stripping close tags.
+ kept.append(cleaned)
+ # else: only punctuation remains (e.g. bare ".") — discard.
+ cleaned = "\n".join(kept)
+
+ combined.append(f"\n\n---\n\n# {relative}\n")
+ combined.append(cleaned.strip())
+
+ output_file.write_text(
+ "\n".join(combined) + "\n",
+ encoding="utf-8",
+ )
+
+
+def setup(app):
+ app.add_css_file('css/custom.css')
+ app.connect("build-finished", generate_combined_markdown)
diff --git a/infrastructure/dc-design/data/concrete-slab-flooring.png b/infrastructure/dc-design/data/concrete-slab-flooring.png
new file mode 100644
index 0000000..9710091
Binary files /dev/null and b/infrastructure/dc-design/data/concrete-slab-flooring.png differ
diff --git a/infrastructure/dc-design/data/dlc-diagram.jpeg b/infrastructure/dc-design/data/dlc-diagram.jpeg
new file mode 100644
index 0000000..58844d5
Binary files /dev/null and b/infrastructure/dc-design/data/dlc-diagram.jpeg differ
diff --git a/infrastructure/dc-design/data/orv3-rack.jpeg b/infrastructure/dc-design/data/orv3-rack.jpeg
new file mode 100644
index 0000000..4e7b5bc
Binary files /dev/null and b/infrastructure/dc-design/data/orv3-rack.jpeg differ
diff --git a/infrastructure/dc-design/data/power-feed-diagram.jpeg b/infrastructure/dc-design/data/power-feed-diagram.jpeg
new file mode 100644
index 0000000..5e5352d
Binary files /dev/null and b/infrastructure/dc-design/data/power-feed-diagram.jpeg differ
diff --git a/infrastructure/dc-design/data/raised-floor-vs-concrete-slab.jpeg b/infrastructure/dc-design/data/raised-floor-vs-concrete-slab.jpeg
new file mode 100644
index 0000000..c047b5b
Binary files /dev/null and b/infrastructure/dc-design/data/raised-floor-vs-concrete-slab.jpeg differ
diff --git a/infrastructure/dc-design/data/rdh-diagram.jpeg b/infrastructure/dc-design/data/rdh-diagram.jpeg
new file mode 100644
index 0000000..f3b74bd
Binary files /dev/null and b/infrastructure/dc-design/data/rdh-diagram.jpeg differ
diff --git a/infrastructure/dc-design/index.rst b/infrastructure/dc-design/index.rst
new file mode 100644
index 0000000..e73ea88
--- /dev/null
+++ b/infrastructure/dc-design/index.rst
@@ -0,0 +1,768 @@
+.. meta::
+ :description: An overview of AMD Instinct data center architecture covering power, cooling, networking, storage, and resiliency design for high-density AI and HPC deployments.
+ :keywords: AMD Instinct, data center, HPC, AI, cooling, power, networking, storage, ORV3, RDHx, DLC, fat tree, rail-optimized
+
+************************************************************************************************************************
+Data Center Design Guide
+************************************************************************************************************************
+
+The rapid evolution of high performance computing (HPC), artificial intelligence (AI) and machine learning (ML) has
+driven significant changes in data center infrastructure. These workloads demand unprecedented compute power, memory
+bandwidth, and interconnect throughput to achieve the performance required for next-generation applications.
+
+As organizations scale these deployments to tackle complex problems—from natural language processing to autonomous
+systems—data centers must evolve to support higher power densities, advanced cooling systems, and robust networking
+fabrics capable of sustaining hundreds of terabits of aggregate bandwidth.
+
+This means the requirements for the data center as we know it must change to accommodate the current high density,
+power, and cooling demands of modern accelerated computing.
+
+Challenges
+========================================================================================================================
+
+A non-exhaustive list of challenges are faced when deploying dense, high-powered racks at modest to large scale. Many of
+these challenges co-exist and compound each other.
+
+Power delivery infrastructure
+------------------------------------------------------------------------------------------------------------------------
+
+Supplying hundreds of kilowatts (kW) per rack requires massive power feeds, high-capacity busbars and redundant power
+distribution units (PDUs), often requiring upgrades to building electrical infrastructure. At these loads, current can
+exceed thousands of amps where low voltage (110-240V) distribution is used, so in the interest of safety and efficiency
+the industry is moving toward higher voltages like 380-415V AC or 48V DC within racks to reduce current and losses.
+Reliability adds further complexity: N+1 or 2N redundancy becomes more difficult and expensive at these scales, and UPS
+and backup power must be migrated and right-sized for extreme loads.
+
+Cooling challenges
+------------------------------------------------------------------------------------------------------------------------
+
+At 300-400KW per rack, there is considerable heat load to be removed. Traditional air cooling is not optimal or even
+feasible at this density, necessitating liquid cooling solutions like direct liquid cooling (DLC) or immersion cooling.
+Maintaining a uniform temperature throughout the system is equally critical, as large discrepancies can cause mechanical
+and thermal stress that leads to premature failures. To support this, cooling infrastructure must scale accordingly, and
+potentially be modularized throughout the constellation of racks, where each unit has its own loop and is joined to the
+overall chiller plant.
+
+Physical space and ancillary rack design
+------------------------------------------------------------------------------------------------------------------------
+
+Solutions like MI430/450/455X 72GPU and higher come in robust racks with quite a weight load to the floor, requiring
+special floor reinforcement and structural considerations. The rack footprint may also differ from the 19 inch standard,
+meaning existing raised floors may not be compatible.
+
+Cable management
+------------------------------------------------------------------------------------------------------------------------
+
+The required power cables, piping for liquid cooling, and large amount of fiber optic cabling for the high bandwidth
+network fabrics all have to be managed with care to allow for proper air flow.
+
+Energy efficiency and sustainability
+------------------------------------------------------------------------------------------------------------------------
+
+If the cooling and power distribution are not built to efficient standards, power usage effectiveness (PUE) may get much
+worse. Heat reuse is also constrained: with the limited range of the primary and secondary liquid cooling loops (18 - 45C
+inlet temperature), reuse opportunities are limited or require additional heat pumps.
+
+Safety and risk management
+------------------------------------------------------------------------------------------------------------------------
+
+Higher energy densities increase fire hazards, requiring mandatory advanced fire suppression, while the high current and
+voltage raise the risk of severe electrical accidents from arc flash. Liquid cooling introduces further potential for
+leaks, requiring robust containment, leak detection and monitoring / alerting. Maintenance personnel need to be trained
+in handling high power feeds, conduits, and cabling. Human interaction in these environments is highly regulated for good
+reason and requires specialized training for any personnel working in the space.
+
+Operational and maintenance complexity
+------------------------------------------------------------------------------------------------------------------------
+
+Technicians need expertise in high voltage systems with liquid cooling, and strict procedures on operating the power
+circuits in these environments. Downtime carries a heavy cost as well: failures at any level of the system can impact
+massive compute capacity, necessitating a regular schedule of predictive maintenance using telemetry from the entire
+system.
+
+Cost implications
+------------------------------------------------------------------------------------------------------------------------
+
+Upfront capital investment (CapEx) in power provisioning, which may include municipal infrastructure work, and cooling
+of data centers at extreme power levels is non-linear compared to traditional deployment. Operating costs (OpEx) follow
+the same pattern: energy costs are nonlinear for high-capacity demands, where fluctuations in power requirements can
+cost more than the actual energy consumed, and complex infrastructure also increases maintenance costs.
+
+Raised floor versus concrete slab
+=================================
+
+The choice between a raised floor or a concrete slab architecture is a critical design decision in modern high-density
+data centers. Each approach has distinct advantages and challenges, particularly for AI and HPC workloads requiring
+extreme power and cooling densities.
+
+Raised floor design
+-------------------
+
+Raised floors create an underfloor plenum typically used for distributing chilled air, power cabling, and sometimes
+liquid cooling pipes. This approach offers several operational advantages. By delivering cold air directly to rack
+intakes through perforated tiles, it simplifies airflow management, while the plenum itself provides concealed pathways
+for power and network cables that reduce clutter. It also affords flexibility, making it easier to reconfigure airflow
+patterns and cable layouts during upgrades.
+
+These benefits diminish under high-density loads. Air cooling beneath raised floors struggles to handle the extreme heat
+loads of modern accelerated computing (in excess of 50 kW per rack), rendering the approach unsuitable for AI clusters.
+The floors must also support heavy racks and liquid cooling equipment, which requires reinforced panels, and routing
+large-diameter coolant pipes underfloor can be both cumbersome and leak-prone.
+
+.. image:: data/raised-floor-vs-concrete-slab.jpeg
+ :alt: Raised floor versus concrete slab layout comparison
+
+Concrete slab design
+--------------------
+
+Concrete slab floors eliminate the underfloor plenum, relying instead on overhead distribution for power, networking,
+and cooling infrastructure. This design plays to the strengths of dense deployments. Its structural strength makes it
+better suited for heavy racks and immersion cooling tanks, and overhead manifolds and busways simplify the integration
+of direct-to-chip or immersion cooling. Moving distribution above the floor also improves airflow management, enabling
+hot and cold aisle containment without underfloor constraints.
+
+The trade-offs center on distribution above the racks. Power and network cables must be routed through overhead trays,
+which can increase visual clutter, and air distribution has to be handled through overhead ducts or in-row cooling units
+rather than a plenum.
+
+.. image:: data/concrete-slab-flooring.png
+ :alt: Example of concrete slab flooring with overhead distribution for power, networking, and cooling
+
+For ultra high-density AI data centers, concrete slab designs are generally preferred due to their
+compatibility with liquid cooling, structural robustness, and simplified integration of modular power
+systems. Raised floors remain viable for moderate-density environments but are increasingly impractical
+where racks exceed 6500lbs (3400kg).
+
+**Comparison**
+
+.. list-table::
+ :header-rows: 1
+ :widths: 20 40 40
+
+ * - Factor
+ - Raised Floor
+ - Concrete Slab
+ * - Cooling approach
+ - Underfloor air distribution; limited for >50 kW/rack.
+ - Overhead cooling manifolds; ideal for liquid cooling.
+ * - Power distribution
+ - Underfloor cabling; limited space for large feeds.
+ - Overhead busways; supports high-power modular feeds.
+ * - Liquid cooling
+ - Difficult to integrate; leak risks.
+ - Natively supports manifolds, RDHx, and DLC.
+ * - Structural load
+ - Limited; requires reinforced panels.
+ - High capacity; ideal for dense racks.
+ * - Scalability
+ - Limited by floor capacity and airflow constraints.
+ - Modular and scalable for multi-megawatt deployments.
+ * - Maintenance
+ - Easy cabling access; complex cooling management.
+ - Simplified liquid cooling; overhead access required.
+ * - Cost
+ - Lower initial cost; limited upgrade path.
+ - Higher upfront cost; better long-term ROI.
+ * - Preferred for
+ - Legacy or mixed-use data centers.
+ - AI, HPC, and ultra-high-density environments.
+ * - Notes
+ - Not optimal for >30 kW per rack or liquid cooling.
+ - Standard for new AI data center construction.
+
+Physical layout
+===============
+
+There are many of ways to lay out a datacenter. But with the higher demands on density and power, the traditional
+organization of rows and racks may need a rethink. More modern design options include POD level modularity to carve the
+whole system into logical units that can be used as a scaling unit.
+
+Patterns of organization
+------------------------------
+
+Rows of racks
+^^^^^^^^^^^^^
+
+Racks are organized in rows according to a logical functional hierarchy, with critical components positioned centrally
+to optimize accessibility and performance. For example, a central networking rack may be co-located with essential
+services such as the control plane, management, and monitoring systems and, where applicable, centralized storage
+resources. This architectural arrangement can be integrated with a range of cooling methodologies, including
+conventional air cooling, contained airflow systems, in-row cooling units, rear door heat exchangers, or hybrid
+configurations that combine direct liquid cooling (DLC), air cooling, and RDHX technologies to meet varying thermal and
+operational requirements.
+
+This is basically the traditional organization of infrastructure in data centers where raised floors are typically used
+to provide a path of air to all the racks.
+
+Rows of racks with RDHx
+^^^^^^^^^^^^^^^^^^^^^^^
+
+Incorporating rear door heat exchangers (RDHx) ensures that the heat discharged from the rack is effectively neutralized
+before entering the room, thereby eliminating or significantly reducing reliance on computer room air conditioning
+(CRAC) systems. This approach facilitates straightforward scalability for high-density environments. This can be used in
+existing datacenters to enhance the cooling capacity beyond what is possible with traditional air cooling. Using RDHX
+will also allow organizing racks front to back reducing the footprint to some extent.
+
+All of this also applies to hybrid configurations using direct to chip cooling (DLC).
+
+Hot/cold aisle islands
+^^^^^^^^^^^^^^^^^^^^^^
+
+Hot aisle isolation is a **thermal management strategy** used in high-density data centers to improve cooling efficiency and
+prevent hot air recirculation. It involves **physically enclosing the hot aisle**—the space where the rear of servers expels
+heated air—so that this hot exhaust air is completely separated from the cold air supply. Although it enables higher
+densities of power and cooling to be handled efficiently, there are practical limits to air cooling, above 45KW per rack
+one should consider other strategies
+
+Modular datacenter approach
+^^^^^^^^^^^^^^^^^^^^^^^^^^^
+
+Shifting the paradigm a little further, departing from physical buildings into a scale-out friendly organization, by
+organizing modular groups in separate physical blocks that can be deployed as units. Where each unit is a self-contained
+block of computational elements, power distribution and cooling handling, which can be stacked, put on concrete slabs,
+with or without an enclosed hall around them. These were introduced by hyperscalers, that scaled up in large chunks of
+compute which needed to be deployed rapidly and cost-effective. Speeding up deployments by years where otherwise new
+buildings needed to be built.
+
+Cooling strategies
+------------------
+
+Hot/cold aisle isolation
+^^^^^^^^^^^^^^^^^^^^^^^^
+
+The strategy rests on a few core principles. Hot aisles are contained with panels, doors, and sometimes a ceiling
+plenum, creating a sealed environment for heated exhaust air. Airflow control then directs the exhaust to return
+ducts or overhead plenums, preventing it from mixing with supply air, while pressure management ensures a proper airflow
+balance between the supply and return paths.
+
+This strategy delivers several benefits. By preventing hot and cold air from mixing, cooling efficiency is improved, reducing the
+load on CRAC (computer room air conditioning) units and enabling higher supply air temperatures that improve chiller
+efficiency. It also supports higher rack density, accommodating power densities exceeding 30-50 kW per rack and, in
+liquid-assisted environments, even higher. Optimizing airflow paths yields energy savings by reducing fan energy and
+cooling costs, and the result is predictable thermal zones that maintain consistent inlet temperatures for IT equipment.
+
+Implementation relies on physical barriers such as doors at aisle ends, roof panels above racks, and sometimes full
+enclosures, with the contained hot air ducted to overhead return plenums or directly to cooling units. These panels and
+doors must comply with fire codes and allow for emergency egress. It is worth noting the distinction between the two
+containment approaches: hot aisle isolation captures and removes hot air efficiently and is often preferred for
+high-density environments, whereas cold aisle containment encloses the cold aisles to protect supply air and is simpler
+but less effective at extreme densities.
+
+
+Rear door heat exchangers (RDHx)
+^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
+
+As data center power densities continue to rise—often exceeding 30-50 kW per rack, traditional computer room air
+conditioning (CRAC) units struggle to keep up. Rear door heat exchangers (RDHx) offer a practical, incremental solution
+to supplement existing air cooling infrastructure.
+
+A rear door heat exchanger is a liquid-cooled radiator mounted on the rear of a server rack, intercepting hot exhaust
+air from servers before it enters the data hall. In doing so it prevents hot air recirculation, reduces CRAC load, and
+supports higher rack densities without major infrastructure changes. The working principle is straightforward: servers
+expel hot air into the rear door enclosure, where coils circulating chilled water or coolant absorb heat from the
+exhaust, and the air then exits the rear door at near-room temperature, minimizing thermal impact on the data hall.
+
+These benefits make RDHx attractive as an incremental upgrade, enhancing existing air-cooled systems without replacing
+CRAC units while enabling racks up to 50-80 kW in some cases. Because it reduces fan power and allows higher chilled
+water temperatures, it improves both energy and chiller efficiency, and it optimizes space by avoiding the need for
+additional in-row cooling units or major floor plan changes. Realizing these benefits depends on a few integration
+considerations: the design requires a secondary cooling loop connected to facility water or a dedicated chiller, leak
+prevention through drip trays, leak detection sensors, and quick-disconnect fittings, rear doors that allow easy service
+without obstructing rack access, and racks and RDHx units that are mechanically and thermally compatible.
+
+There are limitations to keep in mind. While effective, RDHx cannot handle the ultra-high densities (>100 kW per rack)
+typical in AI clusters, it adds liquid cooling infrastructure with the associated plumbing complexity and need for
+skilled maintenance, and it carries a higher upfront cost than pure air cooling. As a result, it is best suited to
+retrofit projects that upgrade legacy data centers to support moderate AI or HPC workloads, and to hybrid cooling
+strategies that combine RDHx with traditional CRAC and containment for balanced performance.
+
+Hybrid cooling approach: DLC and air cooling with hot aisle or in-row cooling
+^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
+
+While direct liquid cooling (DLC) effectively removes heat from high-power components (CPUs, GPUs), residual heat
+from other server components still requires airflow management. A hybrid approach combining DLC with hot aisle
+containment or in-row cooling units addresses this challenge.
+
+The concept pairs two stages of cooling:
+
+* **Primary cooling** is handled by DLC, where cold plates installed on processors and accelerators remove 60-80% of the
+ rack heat load at the source.
+* **Secondary cooling** handles the remaining heat with optimized airflow systems supported by containment or in-row
+ cooling units.
+
+The DLC stage relies on cold plates mounted on CPUs, GPUs, and other high-power chips, with a liquid loop circulating
+coolant to facility water or heat exchangers; by reducing exhaust air temperature it enables higher rack densities.
+
+Hot aisle containment complements this by sealing the hot aisle to prevent mixing of hot and cold air and directing hot
+air to return ducts or cooling units, which improves CRAC performance and reduces fan energy. Where more localized
+handling is needed, in-row cooling units positioned between racks capture and cool hot air before it mixes with room
+air, working in tandem with containment to maintain stable inlet temperatures and scaling for pods or zones with varying
+densities.
+
+There are several benefits to hybrid cooling this way:
+
+* Supports high-density racks of up to 50-100 kW without full immersion cooling.
+* Improves energy efficiency by reducing reliance on CRAC units and lowering PUE.
+* Offers an incremental upgrade path ideal for retrofitting existing air-cooled environments.
+* Provides operational flexibility for mixed workloads and modular pod designs.
+
+Proper implementation depends on the careful design of several essential components:
+
+* Airflow management must ensure proper pressure balance between the DLC and air systems.
+* Leak detection must include sensors and quick-disconnect fittings for the liquid loops.
+* Intelligent controls must monitor temperature, flow, and humidity.
+* N+1 redundancy must be implemented across both the liquid and air systems.
+
+In practice this approach fits AI training clusters with high GPU density that require liquid cooling for the chips and
+air for residual heat, HPC environments with mixed compute nodes and varying thermal profiles, and retrofit projects
+that upgrade legacy data centers without full immersion systems.
+
+Hybrid cooling approach: DLC and RDHx
+^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
+
+This hybrid approach combines direct liquid cooling (DLC) and rear door heat exchangers (RDHx) to offer a powerful,
+incremental strategy for managing extreme heat loads in high-density AI and HPC environments.
+
+The approach works in two stages. The first stage is direct liquid cooling (DLC) inside the server, where cold plates
+are installed on high-heat components such as CPUs and GPUs and a primary liquid loop circulates coolant through the
+plates, removing 60-80% of the heat load at the component level. This drastically reduces the temperature of exhaust air
+leaving the server.
+
+.. image:: data/dlc-diagram.jpeg
+ :alt: Direct contact liquid cooling (DCLC) diagram
+
+(DCLC = Direct Contact Liquid Cooling)
+
+The second stage adds a rear door heat exchanger (RDHx) at the rack level. Mounted on the rear of the rack, it captures
+residual heat from the exhaust air and a secondary liquid loop transfers this heat to facility water or a dedicated
+chiller, so the air exiting the rack is near ambient temperature, minimizing thermal impact on the data hall.
+
+.. image:: data/rdh-diagram.jpeg
+ :alt: Rear door heat exchanger (RDHx) diagram
+
+Combining the two stages brings several benefits:
+
+* Enhanced cooling capacity supporting racks up to 50-100 kW, far beyond traditional air-cooling limits.
+* Energy efficient, reducing CRAC load and allowing higher chilled water temperatures, improving overall PUE.
+* An incremental upgrade path, ideal for retrofitting existing air-cooled environments without full immersion systems.
+* Flexibility for mixed workloads—AI clusters, HPC nodes, and standard servers.
+
+Realizing these benefits depends on a few key design considerations:
+
+* Dual liquid loops: a primary loop for DLC and a secondary loop for RDHx, which can share heat rejection infrastructure.
+* Leak management using drip trays, leak sensors, and quick-disconnect fittings for safety.
+* Rack compatibility, ensuring racks can support RDHx weight and plumbing.
+* Monitoring and control with intelligent sensors for flow, temperature, and pressure in both loops.
+
+In practice, this approach suits high-density retrofits that upgrade legacy data centers to support AI or HPC without a
+full redesign, as well as hybrid cooling zones that combine DLC and RDHx in pods for scalable, modular deployments.
+
+A new chapter: moving to open standards-based units
+^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
+
+Open rack version 3 (ORV3) is an open standard developed by the Open Compute Project (OCP) to address the
+infrastructure challenges of modern high-density AI and HPC deployments.
+
+The move to ORV3 is driven by several pressures that traditional racks cannot meet:
+
+* Scalability for AI and HPC: Traditional 19-inch racks cannot efficiently support racks exceeding 50-100+ kW.
+* Standardization: Promotes interoperability across vendors, reducing vendor lock-in.
+* Efficiency: Optimized for liquid cooling, high-voltage busbars, and modular power shelves.
+* Sustainability: Designed for better airflow, liquid cooling integration, and reduced material waste.
+
+At the heart of the standard is a rethink of how power is delivered inside the rack. Several key features set
+ORV3 apart:
+
+* 48V-56V DC power distribution inside the rack using a busbar.
+* No PSUs inside the individual servers/server trays.
+* Moves away from traditional 110/240V AC PDU systems to bulk DC conversion, reducing current and cable losses.
+* Supports modular power shelves and busbars for easy scaling.
+
+The physical form factor changes as well. ORV3 racks are 21-inch wide (vs. 19-inch EIA standard), allowing more
+space for airflow and components, with depth optimized for large GPUs and accelerators. This comes with additional
+weight not suitable for traditional raised floors.
+
+Cooling is treated as a first-class concern. The standard provides native support for liquid cooling manifolds, rear
+door heat exchangers, and direct-to-chip cooling, along with improved airflow paths for hybrid cooling strategies.
+
+For the most demanding workloads, ORV3 also defines a double-wide variant. This double-width version of the ORV3 rack
+is built for GPU-dense servers and large accelerator trays, making it ideal for multi-node AI training clusters where
+interconnect bandwidth and cooling are critical.
+
+Adopting ORV3 brings several benefits:
+
+* Future-proofing: Supports next-gen AI hardware with massive power and cooling needs.
+* Operational efficiency: Simplifies deployment and maintenance with modular components.
+* Vendor ecosystem: Backed by OCP, ensuring broad industry support and innovation.
+
+.. image:: data/orv3-rack.jpeg
+ :alt: ORV3 open rack standard unit
+
+Network Design
+=========================================================================================================================
+
+When we consider networking in HPC and AI deployments, we split this up into functional elements: the different
+networks that exist in a cluster, the physical topology, and the software-defined elements.
+
+Network types
+-------------------------------------------------------------------------------------------------------------------------
+
+A cluster carries several distinct classes of traffic, and each is served by its own network. These fabrics have
+different needs in terms of bandwidth, availability, topology, and quality of service, and may even use different
+physical media:
+
+* **Management network / out of band network** is typically isolated from the public network and reserved for internal
+ traffic to manage the cluster nodes (BMC, switch management), without exposing sensitive management traffic to users.
+* **Public access network** is where users and applications communicate. It is typically lower bandwidth, as it only
+ provides access to services (interactive sessions, web interfaces) rather than bulk data transfer.
+* **Storage network** is a high bandwidth and preferably highly available fabric that scales to the needs of the
+ clusters being deployed and the types of storage being used.
+* **High speed, low latency interconnect for accelerators (backend fabric)** focuses on high bandwidth and low
+ latency, providing RDMA access between endpoints for fast communication in AI and HPC workloads.
+
+The backend fabric topology currently is based on two types: fat tree and rail-optimized.
+
+Fat tree topology
+-------------------------------------------------------------------------------------------------------------------------
+
+A fat tree topology is a hierarchical network architecture commonly used in high-performance computing (HPC) and AI
+clusters. It is designed to provide high bandwidth, low latency, and scalability by connecting nodes through multiple
+layers of switches. It is the easiest to deploy, but not the most cost-effective, and has a limitation on connected
+endpoints due to the number of switch ports available in the fabric.
+
+Several characteristics define the topology:
+
+* Composed of multiple layers in a hierarchical structure: core, aggregation, and edge (leaf). Each layer connects to the
+ next in a tree-like fashion.
+* Equal-cost multipath: Multiple paths exist between any two endpoints, enabling load balancing and fault tolerance.
+* Oversubscription reduction: Unlike a simple tree, fat tree increases link capacity toward the root, ensuring
+ aggregate bandwidth is maintained.
+
+The switching elements are typically implemented using commodity switches arranged in pods, and often use Clos network
+principles for non-blocking connectivity. Traffic flows through the layers as follows:
+
+* Core layer: Provides interconnection between aggregation layers across pods.
+* Spine/Aggregation layer: Connects leaf switches to the core.
+* Leaf layer: Connects directly to servers.
+* Each upward link in the hierarchy is "fatter" (higher bandwidth or more parallel links) than the downward links.
+
+This arrangement brings a couple of key advantages:
+
+* Scalability: Supports thousands of nodes with predictable performance.
+* High bandwidth: Multiple paths reduce congestion.
+
+Fat tree topologies are well suited to HPC clusters, AI training fabrics, and large-scale data centers using Ethernet or
+InfiniBand.
+
+Rail-optimized
+-------------------------------------------------------------------------------------------------------------------------
+
+A Rail-optimized topology is a network architecture designed specifically for AI and HPC clusters to maximize
+throughput and minimize latency for GPU-to-GPU communication. It is increasingly used in large-scale training
+environments where efficient collective communications (e.g., all-reduce) are critical.
+
+Traditional topologies like fat-tree or Clos are general-purpose and optimized for east-west traffic across the entire
+cluster. Rail-optimized designs instead focus on high-throughput, low-latency links along "rails" of GPUs, ensuring
+efficient data exchange within tightly coupled compute groups. This is reflected in its characteristics:
+
+* Linear or semi-linear structure: GPUs are grouped into "rails" (rows or chains) with direct, high-bandwidth
+ connections between adjacent nodes.
+* Often implemented using InfiniBand, or high-speed Ethernet fabrics.
+* Optimized for collective operations.
+
+AI workloads rely heavily on all-reduce and broadcast operations. Rail topology minimizes hop count and latency for
+intra-rail communication while allowing controlled inter-rail traffic via spine nodes. Rails can be combined with
+spine-leaf or Clos networks for inter-rail communication, typically connecting at the spine level, where traffic
+between different GPU groups is routed.
+
+This design delivers high efficiency for AI training by reducing synchronization overhead for large-scale models, and
+predictable performance through dedicated paths for GPU clusters that avoid congestion. It scales to thousands of GPUs
+with minimal latency impact, making it a good fit for large AI clusters (e.g., LLM training, recommendation systems,
+video processing) and HPC environments with tightly coupled compute nodes.
+
+Centralized control plane
+=========================================================================================================================
+
+As high-performance computing (HPC) and AI factories scale to thousands of nodes and petaflops of compute, managing
+infrastructure manually becomes infeasible. A centralized control plane provides the operational backbone to
+orchestrate, monitor, and optimize all infrastructure components—from compute and networking to power and cooling—in a
+unified, automated framework.
+
+Key objectives
+-------------------------------------------------------------------------------------------------------------------------
+
+The control plane is built around a handful of core objectives:
+
+* Unified management: Single pane of glass for all infrastructure layers.
+* Dynamic resource allocation: Optimize GPU, CPU, and memory utilization for AI/HPC workloads.
+* Policy enforcement: Apply security, compliance, and workload placement policies globally.
+* Telemetry & analytics: Real-time monitoring of power, cooling, and performance metrics.
+
+Core components
+-------------------------------------------------------------------------------------------------------------------------
+
+Several components work together to deliver these objectives. The orchestration layer integrates with job schedulers
+(e.g., Slurm for AI workloads) and handles workload placement based on resource availability and thermal constraints.
+Underneath it, an infrastructure abstraction layer pools compute, storage, and network resources and supports
+heterogeneous hardware (GPUs, CPUs, FPGAs, accelerators).
+
+Observability and integration are provided by two further components:
+
+* Telemetry & monitoring collects data from rack-level sensors, PDUs, cooling loops, and servers, enabling predictive
+ analytics for failure prevention and energy optimization.
+* Control APIs provide RESTful interfaces for automation tools and AI-driven optimizers, with northbound interfaces for
+ enterprise IT and southbound interfaces for hardware controllers.
+
+Running across all of these, a security and compliance layer implements role-based access control (RBAC) and zero-trust
+networking, and ensures compliance with data sovereignty and industry standards.
+
+Benefits
+-------------------------------------------------------------------------------------------------------------------------
+
+Centralizing control in this way brings several benefits:
+
+* Operational efficiency: Reduces manual intervention and accelerates deployment.
+* Energy optimization: Dynamically adjusts workloads based on power and cooling availability.
+* Scalability: Supports multi-megawatt facilities and thousands of nodes.
+* Resilience: Enables rapid failover and disaster recovery through centralized policies.
+
+Integration with AI workloads
+-------------------------------------------------------------------------------------------------------------------------
+
+For AI workloads specifically, the control plane coordinates GPU scheduling (allocating GPUs for training and inference
+based on priority and thermal limits), data pipeline management (coordinating storage and compute for large-scale
+datasets), and model lifecycle control (tracking training, validation, and deployment stages).
+
+Future trends
+-------------------------------------------------------------------------------------------------------------------------
+
+Looking ahead, several trends are shaping the evolution of the control plane:
+
+* AI-driven control plane: Predictive orchestration using machine learning.
+* Federated control: Multi-site coordination for global AI factories.
+* Integration with liquid cooling telemetry: Real-time thermal optimization.
+
+Storage
+=========================================================================================================================
+
+High-performance computing (HPC) and AI workloads generate and consume massive datasets, often reaching petabytes in
+scale. Meeting these demands requires a storage architecture that delivers extreme throughput, low latency, and seamless
+scalability.
+
+Centralized storage
+-------------------------------------------------------------------------------------------------------------------------
+
+A centralized, modular storage system provides a unified platform for data access while enabling incremental scaling to
+support growing workloads. Its design rests on a few key principles.
+
+AI training and HPC simulations require multi-terabit bandwidth and microsecond-level latency, so high throughput and
+low latency come first. Options include:
+
+* Parallel file systems (e.g., Lustre, IBM Spectrum Scale, BeeGFS) for distributed I/O.
+* Object-based filesystems born out of the "big data" period (e.g., Ceph, MinIO, Scality).
+* Enterprise class scale out NAS (caveat: performance profile needs to match the workload).
+
+The architecture is modular, with storage deployed in pods or building blocks that each add capacity and performance,
+enabling incremental scaling without disrupting operations. Data is organized into tiers to balance performance against
+cost:
+
+* Hot tier: NVMe SSDs for active datasets and model checkpoints.
+* Warm tier: High-capacity HDD arrays for intermediate data.
+* Cold tier: Object storage or tape for archival and compliance.
+
+A centralized control plane ties it together, providing unified management for provisioning, monitoring, and policy
+enforcement, and integrating with orchestration tools for AI/HPC workloads.
+
+Several core components make up the system:
+
+* Storage nodes: Compute-capable nodes running parallel file systems.
+* High-speed interconnect: InfiniBand or 400G Ethernet for low-latency data access.
+* Metadata servers: Scalable architecture to handle billions of files efficiently.
+* Caching layers: Client-side or in-network caching for performance optimization.
+
+The platform grows through horizontal scaling (adding storage pods to increase capacity and throughput), namespace
+expansion (maintaining a single global namespace across clusters), and data striping (distributing data across multiple
+nodes for parallel access). It integrates with AI and HPC workflows through fast checkpointing and recovery for model
+checkpoints during training, data preprocessing that co-locates compute and storage to reduce data movement, and
+multi-tenancy that isolates workloads while sharing infrastructure efficiently.
+
+Taken together, this delivers several benefits:
+
+* Performance: Sustains high IOPS and bandwidth for large-scale jobs.
+* Flexibility: Modular design supports incremental growth.
+* Reliability: Redundant paths and erasure coding ensure data integrity.
+* Cost efficiency: Tiered storage optimizes cost per GB for different data types.
+
+Looking ahead, NVMe-over-Fabrics (NVMe-oF) promises ultra-low latency, AI-driven storage management will enable
+predictive scaling and optimization, and tighter integration with cloud and edge will support hybrid HPC/AI
+deployments.
+
+Federated storage
+-------------------------------------------------------------------------------------------------------------------------
+
+As AI training clusters scale to thousands of GPUs, centralized storage alone can become a bottleneck. Federated
+storage addresses this by distributing storage across pods, each tailored for the compute resources it serves—while
+maintaining a unified logical view across the cluster. A few design principles underpin this approach.
+
+Storage is provisioned at the pod level: each pod includes a dedicated high-performance storage subsystem co-located
+with compute nodes, designed to sustain extreme I/O rates for a single training job without relying on external
+bandwidth. These pods are organized into a hierarchical federation:
+
+* Local tier: NVMe-based storage within the pod for active datasets and checkpoints.
+* Regional tier: Aggregated storage across multiple pods for shared datasets.
+* Global tier: Centralized or cloud-integrated storage for archival and multi-job access.
+
+A logical namespace spans all tiers for seamless data access, with metadata distributed hierarchically to minimize
+latency for local operations. Inter-pod communication uses lower-bandwidth links for synchronization and dataset
+sharing between pods, optimized for checkpoint exchange and model parameter updates rather than bulk data transfer.
+
+This architecture brings several benefits:
+
+* Performance isolation: Each pod achieves maximum I/O performance for its assigned training instance.
+* Scalability: Pods can be added incrementally without saturating global storage.
+* Resilience: Local storage reduces dependency on WAN links and central systems.
+* Flexibility: Supports hybrid workloads and federated learning scenarios.
+
+Integration with AI training is done by dedicating a single training instance per pod (aligning compute and storage resources
+for optimal throughput), using fast local writes for checkpointing with asynchronous replication to higher tiers, and
+performing data preprocessing locally to minimize inter-pod traffic. Future enhancements include intelligent,
+AI-driven data placement to decide which tier stores which data, NVMe-over-fabrics for intra- and inter-pod
+acceleration, and federated learning support for secure aggregation across pods without moving raw data.
+
+Power considerations
+==========================================================================================================================
+
+Power feed
+-------------------------------------------------------------------------------------------------------------------------
+
+Modern AI and HPC workloads demand extreme power densities, often reaching 150-400 kW per rack and scaling to
+multi-megawatt or gigawatt-level facilities. Designing a reliable, efficient, and scalable power feed system is critical
+to sustaining these workloads without compromising performance or safety.
+
+Key design principles
+-------------------------------------------------------------------------------------------------------------------------
+
+High voltage distribution keeps transmission losses down: medium-voltage feeds (4.16 kV-34.5 kV) from the utility or an
+on-site substation are stepped down to 415V AC or 380V DC at the data hall for rack-level distribution, and the higher
+voltage reduces current, enabling smaller conductors and improved efficiency.
+
+The power architecture is modular, built from a few repeatable elements:
+
+* Pod-level power zones: Group racks into pods (1–5 MW each) with dedicated feeds.
+* Overhead busways: Replace heavy cabling with busbars for flexible tap-offs.
+* Power shelves: Integrated into ORV3 racks for 48V DC distribution to IT gear.
+
+Redundancy is layered throughout to keep power available through faults and disturbances:
+
+* N+1 or 2N configurations: Dual independent feeds from separate substations or generators.
+* Automatic transfer switches (ATS) for seamless failover.
+* Battery energy storage systems (BESS) for ride-through and peak shaving.
+* In-rack power resilience (supercap shelves to provide local instantaneous power resilience).
+
+The design must also anticipate growth—use modular PDUs and busways to add capacity incrementally and support future
+workloads exceeding 300 kW per rack without major redesign. High-power feed systems are composed of several core
+components:
+
+* Main switchgear: Interfaces with utility or on-site generation.
+* Transformers: Step down medium voltage to distribution voltage.
+* Busway systems: Overhead or underfloor for flexible rack connections.
+* Rack-level PDUs: Intelligent units for monitoring and load balancing.
+* Monitoring & control: Real-time telemetry for voltage, current, and power quality.
+
+.. image:: data/power-feed-diagram.jpeg
+ :alt: High-power data center power feed architecture diagram
+
+Integration with cooling
+-------------------------------------------------------------------------------------------------------------------------
+
+Power and cooling must be co-designed. Liquid cooling loops often share pathways with busways, and heat recovery
+systems can leverage electrical infrastructure for energy reuse.
+
+Safety considerations
+-------------------------------------------------------------------------------------------------------------------------
+
+Safety spans several disciplines: arc flash protection through barriers and PPE protocols, grounding and bonding that
+comply with electrical codes, and fire suppression using systems compatible with electrical equipment.
+
+Future trends
+-------------------------------------------------------------------------------------------------------------------------
+
+Several trends are shaping the future of power feed design:
+
+* Direct DC distribution: Reduces conversion losses and improves efficiency.
+* Renewable integration: Solar and wind feeding on-site microgrids.
+* AI-driven power management: Predictive load balancing and fault detection.
+
+Power resiliency
+=========================================================================================================================
+
+Data centers operating at hundreds of kilowatts per rack and scaling to multi-megawatt or gigawatt levels face unique
+challenges in maintaining continuous power availability. Even brief outages can disrupt AI training jobs, corrupt model
+checkpoints, and result in significant financial losses.
+
+Key strategies
+-------------------------------------------------------------------------------------------------------------------------
+
+Resiliency starts with a redundant power architecture: N+1 or 2N redundancy provides dual independent feeds from
+separate substations or utility grids, and isolated, pod-level power zones contain faults and simplify failover. This
+is backed by on-site energy storage:
+
+* Battery energy storage systems (BESS): Provides ride-through capability during grid disturbances.
+* Flywheel systems: Ultra-fast response for short-duration outages.
+* Integration with UPS: High-capacity UPS systems designed for extreme loads. Only supply the core systems with UPS
+ protection; this would include switching, storage and control plane infrastructure.
+
+For longer outages, backup power generation takes over, using diesel or gas generators sized for multi-megawatt loads
+with rapid start capability, or hybrid solutions that combine generators with battery storage for seamless
+transitions. At the facility level, grid interaction and microgrids provide further resilience:
+
+* On-site substations: High-voltage feeds (230-500 kV) for large-scale facilities.
+* Microgrid architecture: Enables local generation and storage to operate independently during grid failures.
+* Renewable integration: Solar and wind sources for sustainability and resilience.
+
+Dynamic load management keeps critical workloads running during power events, using AI-driven control systems with
+predictive algorithms to balance loads and prioritize critical workloads, and load shedding policies that gracefully
+degrade non-critical services. Underpinning all of this, monitoring and fault detection provides real-time telemetry of
+voltage, current, and power quality, predictive maintenance that detects anomalies before failures occur, and automated
+failover that switches between power sources without manual intervention.
+
+Together these strategies deliver operational continuity that minimizes downtime for mission-critical AI/HPC workloads,
+risk mitigation that reduces exposure to grid instability and catastrophic failures, and scalability that supports
+incremental growth without compromising resilience.
+
+Legal information
+========================================================================================================================
+.. Font size styling for legal text is located in reference-architecture/MI3XX/_static/css/custom.css
+.. container:: legal-text
+
+ DISCLAIMER
+
+ The information contained herein is for informational purposes only, and is subject to change without notice.
+ While every precaution has been taken in the preparation of this document, it may contain technical inaccuracies,
+ omissions and typographical errors, and AMD is under no obligation to update or otherwise correct this information.
+ Advanced Micro Devices, Inc. makes no representations or warranties with respect to the accuracy or completeness of the
+ contents of this document, and assumes no liability of any kind, including the implied warranties of noninfringement,
+ merchantability or fitness for particular purposes, with respect to the operation or use of AMD hardware, software or
+ other products described herein. No license, including implied or arising by estoppel, to any intellectual property
+ rights is granted by this document. Terms and limitations applicable to the purchase or use of AMD's products are as
+ set forth in a signed agreement between the parties or in AMD's Standard Terms and Conditions of Sale. GD-18
+
+ COMPLIANCE WITH LAWS
+
+ Customer shall adhere to all applicable export laws and regulations including, without limitation, those
+ administered by the U.S. Department of Commerce - Bureau of Industry and Security (U.S. Export Administration
+ Regulations 15 CFR 730 et seq.) and those administered by the U.S. Department of State in accordance with the U.S.
+ International Traffic in Arms Regulations (ITAR) set forth in Subchapter M, Title 22, Code of Federal Regulations, Parts
+ 120 through 130 (22 CFR 120-130), as the same may be amended from time to time, and shall not export, re-export, resell,
+ transfer, or disclose, directly or indirectly, any Products or technical data, or the direct product of any Products or
+ technical data, to any proscribed person, entity, or country, or foreign national thereof, unless properly authorized by
+ the U.S. government and/or any other applicable or relevant government or regulatory body, including the export
+ authorities of all respective countries. For the avoidance of doubt, Customer shall not use Products in, or re-export
+ Products to Belarus, Russia and the Donetsk (DNR) or Luhansk (LNR) regions of Ukraine, regardless of the applicable
+ export laws and regulations. Customer shall impose upon its customers terms at least as restrictive as those contained
+ in this Clause 14 with respect to any sale, distribution or export of Products.
+
+ © 2026 Advanced Micro Devices, Inc. All rights reserved. AMD, the AMD Arrow logo, and combinations thereof are
+ trademarks of Advanced Micro Devices, Inc. Other product names used in this publication are for identification purposes
+ only and may be trademarks of their respective companies.
+
diff --git a/infrastructure/dc-design/llms.txt b/infrastructure/dc-design/llms.txt
new file mode 100644
index 0000000..d93a8d5
--- /dev/null
+++ b/infrastructure/dc-design/llms.txt
@@ -0,0 +1,18 @@
+# AMD Instinct Data Center Design Guide
+
+> An overview of AMD Instinct data center architecture for high-density AI and HPC deployments. Covers the challenges of dense, high-powered racks, raised floor versus concrete slab construction, physical layout and cooling strategies (hot/cold aisle isolation, RDHx, DLC, and hybrid approaches), ORV3 open-standard racks, backend network design (fat tree and rail-optimized topologies), centralized control planes, centralized and federated storage, and power feed and resiliency design.
+
+## Topics
+
+- [Challenges](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#challenges): Compounding challenges of dense, high-powered racks—power delivery, cooling, physical space and floor loading, cable management, energy efficiency and PUE, safety and risk, operational complexity, and non-linear CapEx/OpEx cost implications.
+- [Raised floor versus concrete slab](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#raised-floor-versus-concrete-slab): Trade-offs between raised floor and concrete slab architectures for cooling, power distribution, liquid cooling, structural load, scalability, and cost, with concrete slab generally preferred for ultra-high-density AI deployments.
+- [Physical layout](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#physical-layout): Patterns of organization (rows of racks, RDHx rows, hot/cold aisle islands, modular datacenters) and cooling strategies including hot/cold aisle isolation, rear door heat exchangers, hybrid DLC plus air or RDHx, and the move to ORV3 open-standard racks.
+- [Network Design](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#network-design): Cluster network types (management/out-of-band, public access, storage, and backend accelerator fabric) and backend fabric topologies, comparing fat tree and rail-optimized designs for AI and HPC workloads.
+- [Centralized Control Plane](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#centralized-control-plane): Unified orchestration, infrastructure abstraction, telemetry and monitoring, control APIs, and security for managing compute, networking, power, and cooling at scale, with integration into AI workloads.
+- [Storage](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#storage): Centralized modular storage and federated pod-level storage architectures, covering parallel and object file systems, tiered storage, scalability strategies, and integration with AI and HPC training workflows.
+- [Power considerations](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#power-considerations): High-voltage and modular power feed design, redundancy and scalability, components of a high-power feed system, integration with cooling, and safety considerations for extreme rack densities.
+- [Power resiliency](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#power-resiliency): Redundant power architecture, on-site energy storage, backup generation, microgrids, dynamic load management, and fault detection for continuous availability of mission-critical AI/HPC workloads.
+
+## Legal
+
+- [Legal information](https://instinct.docs.amd.com/projects/dc-design/latest/index.html#legal-information): Disclaimer, compliance with export laws, and trademark notices.
diff --git a/infrastructure/dc-design/sphinx/_toc.yml.in b/infrastructure/dc-design/sphinx/_toc.yml.in
new file mode 100644
index 0000000..bf35eec
--- /dev/null
+++ b/infrastructure/dc-design/sphinx/_toc.yml.in
@@ -0,0 +1,5 @@
+defaults:
+ numbered: False
+ maxdepth: 6
+root: index
+title: AMD Data Center Design Guide
\ No newline at end of file
diff --git a/reference-architecture/MI3XX/.readthedocs.yaml b/reference-architecture/MI3XX/.readthedocs.yaml
index 731cdab..eeab782 100644
--- a/reference-architecture/MI3XX/.readthedocs.yaml
+++ b/reference-architecture/MI3XX/.readthedocs.yaml
@@ -10,14 +10,14 @@ build:
jobs:
post_checkout:
# Monorepo guard: cancel the build unless this change touched reference-architecture/MI3XX/
- - git fetch origin develop --depth 1 || true
+ # Fetch develop's history (not just its tip) so the common ancestor with
+ # this branch is reachable, then review every commit since that ancestor.
+ - git fetch origin develop || true
- |
- if [ "$READTHEDOCS_VERSION_TYPE" = "external" ]; then
- BASE=origin/develop # PR build: compare against the develop base
- else
- BASE=HEAD^ # branch/tag build (latest): compare against previous commit
- fi
- if git diff --quiet "$BASE" HEAD -- reference-architecture/MI3XX/; then
+ BASE=$(git merge-base origin/develop HEAD || true)
+ # Fail open: if no common ancestor is found (e.g. develop history not
+ # fetched on a PR build), build rather than risk cancelling wrongly.
+ if [ -n "$BASE" ] && git diff --quiet "$BASE" HEAD -- reference-architecture/MI3XX/; then
exit 183
fi
python:
diff --git a/reference-architecture/MI3XX/_static/css/custom.css b/reference-architecture/MI3XX/_static/css/custom.css
index bcbccbd..7f5087e 100644
--- a/reference-architecture/MI3XX/_static/css/custom.css
+++ b/reference-architecture/MI3XX/_static/css/custom.css
@@ -1,3 +1,12 @@
+/* Disable the instinct-design theme's scroll-reveal animation: its JS sets
+ sections to opacity:0 until scrolled into view, which makes long pages
+ appear to "load in" on scroll. Force all sections fully visible so the
+ whole page renders at once (matching the old "instinct" flavor). */
+.bd-main section[id] {
+ opacity: 1 !important;
+ transform: none !important;
+}
+
/* Hide the primary sidebar toggle (carat) only when the primary sidebar is
empty. */
.bd-container__inner:has(.bd-sidebar-primary.hide-on-wide) .sidebar-toggle.primary-toggle {
diff --git a/reference-architecture/MI3XX/conf.py b/reference-architecture/MI3XX/conf.py
index a69cb94..009351b 100644
--- a/reference-architecture/MI3XX/conf.py
+++ b/reference-architecture/MI3XX/conf.py
@@ -22,7 +22,7 @@
html_theme = "rocm_docs_theme"
html_theme_options = {
- "flavor": "instinct",
+ "flavor": "instinct-design",
"show_toc_level": 2,
"navbar_align": "content",
"link_main_doc": True,